4)Refrigerant clearing (Purge) procedure

◆  Always perform the purge procedure after completing recovery.
  The recovery machine may be damaged if any refrigerant is left in the machine.

Close

Close

Close

Open

6

4

ON

ON

Run

Close

High

Close

5

Close

Low

VAPOR

RECOVERY

PURGE

START

OFF

LIQUID

RECOVERY

Liquid valve

Low

High

Vapor valve

System to be recovered

Manifold

(optional accessory)

V240SP

Recovery cylinder

with float sensor

Filter

Safety cable

3

Start switch

2

Power switch

1

Auto stop/run

switch

Slo

w

ly

OFF

6

2kg/cm

2

  /  29psi

or less

◆  Wear  protective  goggles  and 

rubber (leather) gloves.

  If refrigerant falls in your eyes or 

touches your skin, it may lead to 
sight loss or cold injury.

①  Set the Auto stop/run switch to the “Run” 

position.

②  Set the Power switch to the “ON” position.
③  Push the Start switch.
*  Please  refer  to “P20 How  to  Restart  the 

Recovery Machine” if the unit does not run 

smoothly and restart the unit

④  Turn  the  valve  of  the  recovery  machine 

slowly to the “③ PURGE” position.

*  Adjust  suction  pressure  with  valve  to 

under 2kg/cm

2

/ 29psi.

⑤  Close Liquid valve of the cylinder immediately 

after suction pressure to vacuum.

*  For restarting, see “page 20 How to Restart 

the Recovery Machine”.

⑥  Set the Power switch to the “OFF” position.

Valve operation

Operation

End of operation

*  There  is  vapor  refrigerant  left  in  the 

recovery  machine  and  the  hose  of  the 

discharge side.

  Connect  the  hose  of  the  discharge  side 

to  an  evacuated  cylinder  to  recover  the 

refrigerant left in the recovery machine and 

the hose.

⑦ Set the valve of the recovery machine to the 

“④ OFF”.

⑧  Disconnect the hoses.
*  Do not left any refrigerant in the recovery 

machine.

⑨  Put  the  cap  back  on  the  connector  of  the 

safety cable on the cylinder.

HOW TO USE

CAUTION

CAUTION

Содержание ECOsaver V240SP

Страница 1: ...REFRIGERANT RECOVERY MACHINE ECOsaver V240SP INSTRUCTION MANUAL Please read this manual before operating...

Страница 2: ...her Air Conditioning Equipment 8 HOW TO USE 10 Preparation before Operation 10 Liquid Vapor Recovery Procedure 12 Push Pull Recovery Procedure 16 Recovery Procedure of R410A or When the Pressure of Re...

Страница 3: ...d smoking during the work in process Cigarette light may creates Carbon Oxy Chloride and ignite fire Use protective eye glass and hand glove when disconnecting hoses If Freon gas was touch your skin o...

Страница 4: ...generator is not large enough it may lead to heating smoking or fire See the machine plate or this manual for the detailed specifications Do not setup the machine at location where gasoline thinner or...

Страница 5: ...por recovery procedure the compressor may be damaged Do not let visitors touch the machine Do not use the machine when the result is unpredictable Do not use the machine for purposes other than the or...

Страница 6: ...he store where the machine was purchased Use our cylinders that are expressly made for recovery and recycling Evacuation should not be done when the Auto stop run switch is at the Auto stop position A...

Страница 7: ...g hose BLUE 152cm Power cord Shoulder strap Filter Valve Auto stop run switch Start switch Tank full lamp Recovery complete lamp VAPOR RECOVERY START PURGE OFF LIQUID RECOVERY COMPONENTS OF THE MACHIN...

Страница 8: ...032F ES006 Shoulder Strap ES253 Power cord ES305 Instruction manual IM0436 Operation manual IM0437 Model ECOsaver V240SP Code No ES641 Recovery method Compressed vapor recovery method Push Pull metho...

Страница 9: ...Cordless Vacuum Pump 1 5CFM VP151 Useful where has no power source Cooling unit CL3 3 8 ES801 Improves the efficiency of recovery in summer climate recovery in a large volume or recovery of R410A by u...

Страница 10: ...ase of refrigerant when Disconnecting hose Quick charging valve A Y18975 Can be used without leaking refrigerant Recovery speed improves without Schrader Charging hose plus with SealRight fitting Vari...

Страница 11: ...o START The temperature of the cylinder may rise when the ambient temperature is high or R410A is recovered Lower the temperature and pressure of the cylinder according to page 11 4 Helpful Informatio...

Страница 12: ...of the system Heat up the accumulator by a heat gun or give it vibration if it is frozen Recover from multiple systems in one time How to avoid rise in temperature and pressure in the cylinder Put the...

Страница 13: ...quid Vapor Recovery Procedure 1 Connection of the hoses and cords System to be recovered Safety cable Manifold Filter When a cylinder with float sensor is used When a cylinder without float sensor is...

Страница 14: ...vacuum set the valve of the recovery machine to the PURGE position When the discharge pressure reaches to vacuum again connect the hose to the liquid port of the cylinder Close the ball valve of the...

Страница 15: ...ecovered Set the valve of the recovery machine to the START position Open Liquid valve of the cylinder and High Pressure valves Liquid side of manifold and the system Valve operation Operation End of...

Страница 16: ...r switch to the ON position Push the Start switch Please refer to P20 How to Restart the Recovery Machine if the unit does not run smoothly and restart the unit Turn the valve of the recovery machine...

Страница 17: ...cannot be applied Ask the manufacturer of the system if not clear 1 Connection of the hoses and cords Safety cable When a cylinder with float sensor is used High Low Safety cable Filter Sight glass op...

Страница 18: ...ition Do not set the Auto stop run switch to the Auto stop position Air may be left in the machine If the Auto stop position is selected the recovery machine will stop automatically Set to the Run pos...

Страница 19: ...RECOVERY position Set the Auto stop run switch to the Auto stop position Make sure there is no liquid flow in the sight glass Valve operation Operation End of operation Set the valve of the recovery m...

Страница 20: ...linder Turn the valve slowly to the VAPOR RECOVERY position Adjust suction pressure with valve to 3 5 kg cm2 43 5 72 5psi Close the vapor valve of the cylinder when the pressure in the cylinder drops...

Страница 21: ...n Set the Power switch of the recovery machine to the OFF position and reset the breaker after approximately 5 minutes Restart the recovery machine according to How to Restart the Recovery Machine 1 W...

Страница 22: ...linder is under this condition and this chart is useful for field operation When a cylinder is almost full with liquid and no vapor the pressure rises rapidly even with a slight increase in temperatur...

Страница 23: ...mp is on and the recovery machine stops when the cylinder is turned upside down Check the overfilling prevention function in case a cylinder with float sensor is used Connect the Safety cable to the c...

Страница 24: ...on Set the Auto stop run switch to the Run position Set the Power switch to the ON position Push the Start switch Make sure the air is sucked f r o m t h e s u c t i o n p o r t and discharged from th...

Страница 25: ...re in the cylinder is high Cool down the cylinder The piston seal is worn out Repair The cylinder valve is damaged Repair The hose has a core depressor Remove the core depressor in the hose The refrig...

Страница 26: ...module Relay Red lamp Tank full Green lamp Reocvery complete lamp Low pressure switch High pressure switch Safety cable Transformer Relay Compressor Thermal protector Circuit breaker Power switch Grou...

Страница 27: ...FLOW DIAGRAM Condenser Suction port Safety valve High pressure switch Discharge port Suction pressure gauge Discharge pressure gauge Low pressure switch Recovery Purge Purge Recovery Check valve Compr...

Страница 28: ...Customer Memo Please ll in for your record in the future The information is helpful for inquiry and ordering parts Products Number Date Purchased Store Purchased the Unit Ver 01 Code No IM0436 V...

Отзывы: