ECOsaver V240SP
13
① Open the low pressure side and the high
pressure side valves of the manifold.
② Set the valve of the recovery machine to the
“⓪ START” position.
③ Disconnect the hose connected to the liquid
port of the cylinder.
* Hold the hose tightly.
④ Open the ball valve of the hose.
⑤ Set the Auto stop/run switch to the “Run”
position.
⑥ Set the Power switch to the “ON” position.
⑦ Push the Start switch
* Do not set the Auto stop/run switch to the
“Auto stop” position.
Air may be left in the machine.
* Let the unit “Auto stop” by error, change
Auto stop/run switch to “Run” and push
Start switch.
⑧ Set the valve of the recovery machine to the
“② VAPOR RECOVERY”.
⑨ When the discharge pressure reaches to
a vacuum, set the valve of the recovery
machine to the “③ PURGE” position.
⑩ When the discharge pressure reaches to
vacuum again, connect the hose to the liquid
port of the cylinder.
Close the ball valve of the hose.
Valve operation
Operation
End of operation
2)Evacuation of the air from the recovery machine and the hoses
8
12
2
Close
Close
Close
Close
High
Open
Disconnect
Connect
9
Run
Liquid valve
Vapor valve
Close
Low
ON
ON
VAPOR
RECOVERY
PURGE
LIQUID
RECOVERY
1
Open
1
Open
4
Hose
3
10
5
Low
High
Hold tightly
System to be recovered
Manifold
(optional accessory)
V240SP
Recovery cylinder
with float sensor
Hose (red) valve
Filter
Safety cable
Auto stop/run
switch
7
Start switch
6
OFF
13
Power switch
START
OFF
11
⑪ Set the Power switch to the “OFF” position.
⑫ Set the valve of the recovery machine to the
“⓪ START” position.
⑬ Close the low pressure side valve of the
manifold.
HOW TO USE