ECOsaver V240SP
14
HOW TO USE
3)Recovery procedure
● Recover from the high pressure side of the system in case of liquid recovery and recover from the
low pressure side in case of vapor recovery.
● Recover from the high pressure side (liquid refrigerant) when a large volume of refrigerant (5kg
or more) is recovered in one time.
◆ Refrigerant inside the system, which is unsure if it is liquid or vapor, to be liquid
recovered with the valve adjusted to “① Liquid recovery” with less suction pressure.
◆ Throttle the valve of the manifold to regulate the suction pressure to approximately
3kg/cm
2
/43.5psi when the pressure in the system is very high in summer or during
vapor recovery.
◆ Use an oil separator when refrigerant with a large amount of oil is recovered.
Close
12
Run
4
Liquid valve
Vapor valve
System to be recovered
Manifold
(optional accessory)
V240SP
Recovery cylinder
with float sensor
Filter
Safety cable
ON
6
Start switch
ON
5
OFF
1
Power switch
Auto stop/run
switch
Slo
wly
Auto stop
10
Close
Open
8
Open
3
Open
3
Low
Open
8
Close
12
OFF
13
Close
12
Low
Open
3
Close
12
High
High
VAPOR
RECOVERY
PURGE
S
lo
w
ly
START
OFF
14
2
7
9
LIQUID
RECOVERY
Adjust suction pressure to
3 〜 5kg/cm
2
/ 43.5 〜 72.5psi
① Switch off the system to be recovered.
② Set the valve of the recovery machine to the
“⓪ START” position.
③ Open Liquid valve of the cylinder and High
Pressure valves (Liquid side) of manifold
and the system.
Valve operation
Operation
End of operation
⑪ When the suction pressure reaches to
-26cmHg/-10inHg, the Recovery complete
lamp is on and the recovery machine stops
automatically.
⑫ Close both the low side and the high side
ports of the system.
⑬ Set the Power switch to the “OFF” position.
⑭ Set the valve of the recovery machine to the
“⓪ START” position.
CAUTION
START
VAPOR
RECOVERY
LIQUID
RECOVERY
VAPOR
RECOVERY
LIQUID
RECOVERY
START
⑨ Turn the valve slowly to the “②VAPOR RECOVERY”
position.
* Adjust suction pressure with valve to
3 ~ 5 kg/cm
2
/ 43.5 ~ 72.5psi.
* The valve position showing in the drawing at
the right is standard for 3kg/cm
2
/ 43.5psi.
* When the cylinder is
full, the Tank full lamp
is on and the recovery
machine stops.
⑩ Set the Auto stop/run
switch to the “Auto
stop” position.
④ Set the Auto stop/run switch to the “Run”
position.
⑤ Set the Power switch to the “ON” position.
⑥ Push the Start switch.
⑦ Turn the valve slowly to the “① LIQUID RECOVERY”
position.
* Adjust suction pressure with valve to
3 ~ 5 kg/cm
2
/ 43.5 ~ 72.5psi.
* T h e v al v e p o s i t i o n
showing in the drawing
at the right is standard
for 3kg/cm
2
/ 43.5psi.
⑧ When liquid recovery
is completed and vapor
recovery starts, open
the valve of the low
pressure side of the manifold and the port
of the low pressure side of the system to be
recovered.