HOW TO USE

3)Recovery procedure

●  Recover from the high pressure side of the system in case of liquid recovery and recover from the 

low pressure side in case of vapor recovery.

●  Recover from the high pressure side (liquid refrigerant) when a large volume of refrigerant (5kg 

or more) is recovered in one time.

◆  Refrigerant  inside  the  system,  which  is  unsure  if  it  is  liquid  or  vapor,  to  be  liquid 

recovered with the valve adjusted to “① Liquid recovery” with less suction pressure.

◆  Throttle the valve of the manifold to regulate the suction pressure to approximately 

3kg/cm

2

/43.5psi when the  pressure in  the  system is  very  high in  summer or  during 

vapor recovery.

◆  Use an oil separator when refrigerant with a large amount of oil is recovered.

Close

12

Run

4

Liquid valve

Vapor valve

System to be recovered

Manifold

(optional accessory)

V240SP

Recovery cylinder

with float sensor

Filter

Safety cable

ON

6

Start switch

ON

5

OFF

1

Power switch

Auto stop/run

switch

Slo

wly

Auto stop

10

Close

Open

8

Open

3

Open

3

Low

Open

8

Close

12

OFF

13

Close

12

Low

Open

3

Close

12

High

High

VAPOR

RECOVERY

PURGE

S

lo

w

ly

START

OFF

14

2

7

9

LIQUID

RECOVERY

Adjust suction pressure to

3 〜 5kg/cm

2

  /  43.5 〜 72.5psi

①  Switch off the system to be recovered.
②  Set the valve of the recovery machine to the 

“⓪ START” position.

③  Open Liquid valve of the cylinder and High 

Pressure  valves  (Liquid  side)  of  manifold 

and the system.

Valve operation

Operation

End of operation

⑪  When  the  suction  pressure  reaches  to 

-26cmHg/-10inHg,  the  Recovery  complete 

lamp is on and the recovery machine stops 

automatically.

⑫  Close  both  the  low  side  and  the  high  side 

ports of the system.

⑬ Set the Power switch to the “OFF” position.
⑭ Set the valve of the recovery machine to the 

“⓪ START” position.

CAUTION

START

VAPOR

RECOVERY

LIQUID

RECOVERY

VAPOR

RECOVERY

LIQUID

RECOVERY

START

⑨  Turn the valve slowly to the “②VAPOR RECOVERY” 

position.

*  Adjust  suction  pressure  with  valve  to 

3 ~ 5 kg/cm

2

/ 43.5 ~ 72.5psi.

*  The valve position showing in the drawing at 

the right is standard for 3kg/cm

2

/ 43.5psi.

*  When  the  cylinder  is 

full, the Tank full lamp 

is on and the recovery 

machine stops.

⑩  Set  the  Auto  stop/run 

switch  to  the “Auto 

stop” position.

④  Set the Auto stop/run switch to the “Run” 

position.

⑤  Set the Power switch to the “ON” position.
⑥  Push the Start switch.
⑦  Turn the valve slowly to the “① LIQUID RECOVERY” 

position.

*  Adjust  suction  pressure  with  valve  to 

3 ~ 5 kg/cm

2

/ 43.5 ~ 72.5psi.

*  T h e   v al v e   p o s i t i o n 

showing in the drawing 

at the right is standard 

for 3kg/cm

2

/ 43.5psi.

⑧  When  liquid  recovery 

is completed and vapor 

recovery  starts,  open 

the  valve  of  the  low 

pressure  side  of  the  manifold  and  the  port 

of the low pressure side of the system to be 

recovered.

Содержание ECOsaver V240SP

Страница 1: ...REFRIGERANT RECOVERY MACHINE ECOsaver V240SP INSTRUCTION MANUAL Please read this manual before operating...

Страница 2: ...her Air Conditioning Equipment 8 HOW TO USE 10 Preparation before Operation 10 Liquid Vapor Recovery Procedure 12 Push Pull Recovery Procedure 16 Recovery Procedure of R410A or When the Pressure of Re...

Страница 3: ...d smoking during the work in process Cigarette light may creates Carbon Oxy Chloride and ignite fire Use protective eye glass and hand glove when disconnecting hoses If Freon gas was touch your skin o...

Страница 4: ...generator is not large enough it may lead to heating smoking or fire See the machine plate or this manual for the detailed specifications Do not setup the machine at location where gasoline thinner or...

Страница 5: ...por recovery procedure the compressor may be damaged Do not let visitors touch the machine Do not use the machine when the result is unpredictable Do not use the machine for purposes other than the or...

Страница 6: ...he store where the machine was purchased Use our cylinders that are expressly made for recovery and recycling Evacuation should not be done when the Auto stop run switch is at the Auto stop position A...

Страница 7: ...g hose BLUE 152cm Power cord Shoulder strap Filter Valve Auto stop run switch Start switch Tank full lamp Recovery complete lamp VAPOR RECOVERY START PURGE OFF LIQUID RECOVERY COMPONENTS OF THE MACHIN...

Страница 8: ...032F ES006 Shoulder Strap ES253 Power cord ES305 Instruction manual IM0436 Operation manual IM0437 Model ECOsaver V240SP Code No ES641 Recovery method Compressed vapor recovery method Push Pull metho...

Страница 9: ...Cordless Vacuum Pump 1 5CFM VP151 Useful where has no power source Cooling unit CL3 3 8 ES801 Improves the efficiency of recovery in summer climate recovery in a large volume or recovery of R410A by u...

Страница 10: ...ase of refrigerant when Disconnecting hose Quick charging valve A Y18975 Can be used without leaking refrigerant Recovery speed improves without Schrader Charging hose plus with SealRight fitting Vari...

Страница 11: ...o START The temperature of the cylinder may rise when the ambient temperature is high or R410A is recovered Lower the temperature and pressure of the cylinder according to page 11 4 Helpful Informatio...

Страница 12: ...of the system Heat up the accumulator by a heat gun or give it vibration if it is frozen Recover from multiple systems in one time How to avoid rise in temperature and pressure in the cylinder Put the...

Страница 13: ...quid Vapor Recovery Procedure 1 Connection of the hoses and cords System to be recovered Safety cable Manifold Filter When a cylinder with float sensor is used When a cylinder without float sensor is...

Страница 14: ...vacuum set the valve of the recovery machine to the PURGE position When the discharge pressure reaches to vacuum again connect the hose to the liquid port of the cylinder Close the ball valve of the...

Страница 15: ...ecovered Set the valve of the recovery machine to the START position Open Liquid valve of the cylinder and High Pressure valves Liquid side of manifold and the system Valve operation Operation End of...

Страница 16: ...r switch to the ON position Push the Start switch Please refer to P20 How to Restart the Recovery Machine if the unit does not run smoothly and restart the unit Turn the valve of the recovery machine...

Страница 17: ...cannot be applied Ask the manufacturer of the system if not clear 1 Connection of the hoses and cords Safety cable When a cylinder with float sensor is used High Low Safety cable Filter Sight glass op...

Страница 18: ...ition Do not set the Auto stop run switch to the Auto stop position Air may be left in the machine If the Auto stop position is selected the recovery machine will stop automatically Set to the Run pos...

Страница 19: ...RECOVERY position Set the Auto stop run switch to the Auto stop position Make sure there is no liquid flow in the sight glass Valve operation Operation End of operation Set the valve of the recovery m...

Страница 20: ...linder Turn the valve slowly to the VAPOR RECOVERY position Adjust suction pressure with valve to 3 5 kg cm2 43 5 72 5psi Close the vapor valve of the cylinder when the pressure in the cylinder drops...

Страница 21: ...n Set the Power switch of the recovery machine to the OFF position and reset the breaker after approximately 5 minutes Restart the recovery machine according to How to Restart the Recovery Machine 1 W...

Страница 22: ...linder is under this condition and this chart is useful for field operation When a cylinder is almost full with liquid and no vapor the pressure rises rapidly even with a slight increase in temperatur...

Страница 23: ...mp is on and the recovery machine stops when the cylinder is turned upside down Check the overfilling prevention function in case a cylinder with float sensor is used Connect the Safety cable to the c...

Страница 24: ...on Set the Auto stop run switch to the Run position Set the Power switch to the ON position Push the Start switch Make sure the air is sucked f r o m t h e s u c t i o n p o r t and discharged from th...

Страница 25: ...re in the cylinder is high Cool down the cylinder The piston seal is worn out Repair The cylinder valve is damaged Repair The hose has a core depressor Remove the core depressor in the hose The refrig...

Страница 26: ...module Relay Red lamp Tank full Green lamp Reocvery complete lamp Low pressure switch High pressure switch Safety cable Transformer Relay Compressor Thermal protector Circuit breaker Power switch Grou...

Страница 27: ...FLOW DIAGRAM Condenser Suction port Safety valve High pressure switch Discharge port Suction pressure gauge Discharge pressure gauge Low pressure switch Recovery Purge Purge Recovery Check valve Compr...

Страница 28: ...Customer Memo Please ll in for your record in the future The information is helpful for inquiry and ordering parts Products Number Date Purchased Store Purchased the Unit Ver 01 Code No IM0436 V...

Отзывы: