Multifunction LCD Digital Timer
Output mode d: Signal OFF delay (Timer resets when power comes ON.)
The control output is ON when the start signal is ON (except when
the power is OFF or the reset is ON.)
The timer is reset when the time is up.
Timing
Power
Start signal input
Output
Basic Operation
Output functions only during start signal input when setting is 0.
Start signal input is disabled during timing.
Output mode E: Interval (timer resets when power comes ON)
Timing starts when the start signal comes ON. The control output is
reset when time is up. While the start signal is ON, the timer starts
when power comes ON or when the reset input goes OFF.
Power
Start signal input
Output
Basic Operation
Timing
Instantaneous output is disabled when setting is 0.
Output mode F: Cumulative (timer does not reset when power comes ON.)
Timing is enabled by start signal (timing is stopped when the start
signal is OFF or when the power is OFF).
A sustained control output is used.
Timing
Timing
Sustained
Power
Start signal input
Output
Basic Operation
Output is instantaneous when setting is 0.
Z mode : ON/OFF - duty adjustable flicker
Timing starts when the reset signal goes ON.
The status of the control output is reversed when time is up (ON at
start).
While the start signal is ON, the timer starts when the power comes
ON or when the reset input goes OFF.
Timing
Cycle time
Timing
ON duty (%)
Timing
ON duty (%)
Timing
Cycle time
Power
Start signal input
Output
Basic Operation
Normal output operation will not be possible if the set time is too
short.
Set the value to at least 100ms (contact output type).
Start signal input is disabled during timing.
Z mode:
Output quantity can be adjusted by changing the cycle time set in the adjustment level to and by changing
the ON duty (%) set value.
Set value shows the ON duty(%) and can be set to a value between 0 and 100 (%). When the cycle time is 0,
the output will always be OFF.
When the cycle time is not 0 and when ON duty has been set to 0(%), the output will always be OFF. When
ON duty has been set to 100 (%), the output will always be ON.