SERIES EHU-750 HUMIDIFIER
Installation - Step 3
STEAM DISTRIBUTION PIPE POSITIONING
In vertical ducts where the air flow is
upward or downward, the steam distribution
pipe(s) must be tilted by 15° sideways.
590
47
,2
d/2
d
30
°
à 4
5°
1
H3
In duct with limited height, the distribution pipe(s) can be
tilted by 30° to get the 80 mm minimum height.
D = Humidification distance
d = Duct diameter
E
XPRESS
P
ACK
The
Armstron
g
®
ExpressPack
is
a
bespoke steam humidification system made to suit
your your configuration and ready to install in a
ventilation duct.
It permits to have vapor trails (evaporation
distance) as short as 600 mm. For further
reference, please contact
Armstron
g
®
or their
authorized agent.
30°