29
Pictures for illustrating purposes only
ALL WORKS CONCERNED WITH ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A SKILLED AND QUALIFIED PERSONNEL
Series EHU-750 steam humidifier in 3 X 575V - 50/60 Hz
EHU-750
Steam production
(Kg/h)
In
Imaxi
Pmaxi
Cylinder size
Steam
Torroidal
( A )
( A )
( KW )
diameter
transformer
wiring
752-5
5
3,8
4,4
4,33
Small
25
Loop
752-8
8
6,1
6,8
6,69
Small
25
Straight through
752-10
10
7,6
8,4
8,26
Small
25
Straight through
752-15
15
11,5
12,5
12,29
Small
25
Straight through
753-20
20
15,3
16,5
16,22
1 x Large
40
Straight through
753-30
30
22,9
24,6
24,19
1 x Large
40
Split
753-30HC
33
25
26,7
26,27
1 x Large
40
Split
754-40
40
30,6
32,6
32,05
2 x Large
40
Straight through
754-50
50
38,2
40,7
40,02
2 x Large
40
Split
754-60
60
45,9
48,7
47,88
2 x Large
40
Split
754-60HC
65
50
53
52,16
2 x Large
40
Split
755-90
90
68,8
72,9
71,68
3 x Large
40
Split
755-90HC
99
76
80,4
79,08
3 x Large
40
Split
Series EHU-750 steam humidifier in 3 X 600V - 50/60 Hz
EHU-750
Steam production
(Kg/h)
In
Imaxi
Pmaxi
Cylinder size
Steam
Torroidal
( A )
( A )
( KW )
diameter
transformer
wiring
752-5
5
3,7
4,3
4,41
Small
25
Loop
752-8
8
5,9
6,6
6,77
Small
25
Straight through
752-10
10
7,3
8,1
8,31
Small
25
Straight through
752-15
15
11
12
12,31
Small
25
Straight through
753-20
20
14,7
15,8
16,21
1 x Large
40
Straight through
753-30
30
22
23,5
24,11
1 x Large
40
Split
753-30HC
33
24
25,7
26,34
1 x Large
40
Split
754-40
40
29,3
31,3
32,11
2 x Large
40
Straight through
754-50
50
36,6
39
40,01
2 x Large
40
Split
754-60
60
44
46,7
47,91
2 x Large
40
Split
754-60HC
65
48
50,9
52,26
2 x Large
40
Split
755-90
90
66
69,8
71,61
3 x Large
40
Split
755-90HC
98
72
76,2
78,19
3 x Large
40
Split
SERIES EHU-750 HUMIDIFIER
Installation - Step 5