Pictures for illustrating purposes only
OPTIONAL TEMPERATURE CONTROL SYSTEM
This system holds the water in the cylinder at a temperature of 65°C to prevent bacteria or
mold from forming in the cylinder(s) even if there is humidity demand.
The optional temperature control system overrides the automatic factory pre-set draining time
where the cylinder(s) is (are) drained by the system after x hours of stop (s.a. page 43)
Note : the humidifier must be switched on (I) for this system to operate.
Installation
Electrical connection
The wiring of the temperature sensor is to be made on terminals 15 & 16 of the X4 connector
of the main board ref: 500102.
Supplied equipment :
1.
1 x 150 mm long stainless steel tube of Ø 25 mm
or Ø 40 mm (according to model of humidifier)
2
1 collar clamp with soldered temperature sensor
and with 3 meter long wire.
SERIES EHU-750 HUMIDIFIER