ECHNICAL SPECIFICATIONS
Operating power Input
230 VAC
±
10% - 50 Hz
±
10%
Fuse 230 V
F315 mA, 20x5
Operating power output
16.5 VAC 25, 40, or 50 VA Transformer
Auxiliary power with 25 VA
13.8 VDC
±
5% Regulated, 0.5A max.
Auxiliary power with 40/50 VA
13.8 VDC
±
5% Regulated, 1A max.
Recommended battery
12 V, 10 Ah max.
Power consumption
91 mA
Loop resistance
Standard Loop
4K7 ohm, 2 %, 0.25 W
2-wire Smokes
560 ohm, 2 %, 0.25 W maximum
Built-in siren driver
2-tone (Temporal and Yelp)
Loop response
Selectable 50 msec or 500 msec
Operating temperature
0 to 49°C / Relative humidity max. 93%
Shipping weight
4.5 kg
CSx75 and Expander current draw data with EOL on the panel
Board
12.5 VDC
Standby
In Alarm
CSx75
60 mA
CSx75 w/ Dialer
105 mA
CS535
35 mA
CS534
72 mA
CS507
68 mA
CS216
64 mA
CS LCD (piezo off)
92 mA
12 mA
62 mA
CS LCD (piezo on)
103 mA
CS LED (piezo off)
78 mA
7 mA
36 mA
CS LED (piezo on)
90 mA