Page 8
The navigation keys allow selecting the menus:
To enter the mode programming: validate the choice « CODE » in the menu « PROGRAM », and enter the code
111
.
5. CONFIGURATION OF THE MEASURES (MENU « INPUTS »)
5.1. Choice of the measure network « NETWRK », « TYPE »
SINGLE
Single phase
3W BAL
3-phase balanced without neutral
4W BAL
3-phase balanced with neutral
If a mesh voltage is connected on the instrument, programme the network 3W BAL.
If a single voltage is connected on the instrument, connect the network 4W BAL.
5.2. Choice of the ranges « RANGE »
Voltage range « RANG U »
173V
173V
L
-
N
(4W BAL or 1PH) 173V
L
-
L
(3W BAL)
600V
600V
L
-
N
(4W BAL or 1PH) 600V
L
-
L
(3W BAL)
Current range « RANG I »
1A
1A
5A
5A
5.3. Entering of the CT/VT ratios « CT VT »
PRI VT / SEC VT
0230 .
Programming of the VT primary and its unit (V or kV)
V
Programming of the VT secondary, without unit
(Do not programme a ratio but the real values)
PRI CT / SEC CT
0005 .
Programming of the CT primary and its unit (A or kA)
A
Programming of the CT secondary, without unit
(Do not programme a ratio but the real values)
PROGRAM
Modification of the language, entering in mode programming.
INPUTS
Configuration of the measure inputs.
RS-485
OUTPUTS
Configuration of the digital data link RS485 (if option present)
Validate to enter the chosen menu.
Configuration of the instrument outputs (relay, analog).
IMPORTANT:
programme the VT ratios in single voltage (if you
have 15kV/100V VTs between lines, programme 8.33kV / 57.7V
for the ratios)