7. CONFIGURATION OF AN ANALOG OUTPUT (MENU « OUTPUTS »)
7.1. Operating mode of an analog output –
general case:
To configure a current output, it is necessary to define:
- the type of output: 4-20mA , 0-20mA, 0 5mA , 0 10mA
- the n° of the parameter attributed to the output (see the list of the parameters)
- the down and full scale for the measured parameter
- the return value for the output in case of error of the instrument.
N.B:
on the setting on tension , the outputs can deliver 22mA during 1s.
Example:
output 4-20mA for Vr from 50kV to 500Kv.
7.2. Configuration of the outputs: procedure to be followed
Choice of the measure to be transmitted « MEAS O »
U13
Choose the measure to be transmitted.
IL1
…
Choice of the output range « OUT RA »
4 20mA
Choice of the output range in current.
0 20mA
Positive scale only in the case of an instrument with the option ‘‘2A’’.
…
Down scale « DOWN S »
0000 .
Enter the value of the measure corresponding to the output down scale.
A
Full scale « FULL S »
0005 .
Enter the value of the measure corresponding to the output full scale.
A
Return value « RETURN »
22mA
Choice of the return value in case of measure error.
20mA
10mA
…
500kV
50kV
4mA
20mA