Page 5
6. USE OF THE « CUT OFF »
The « cut off » is a programming option of the instrument which allows setting the display to 0 separately for low U
and I values (see the chapter « programming of the
CUT OFF
»).
Once the menu is validated the instrument will measure the values on its inputs and enforce the display to 0 for any
values lower than the « cut off » programmed in % of the caliber (1 or 5A, 100V
L-N
/ 175V
L-L
or 330V
L-N
/ 600V
L-L
).
7. LIST OF THE ERRORS
When the green LED on the front face is blinking, the instrument is indicating an error.
The number of the error can be seen connecting the micro-console or the PC software.
Err nr
Types of errors
Notes
0
Programme memory deleted
Contact after sales
2
Wiring error
Wrong wiring of the U / I measure signals
4
Current caliber overstepping
CC’s not adapted
8
Voltage caliber overstepping
VT’s not adapted – wiring error – error in the
programming of the network type
32
Configuration lost
Re-programme the instrument
64
Calibration lost
Return to the factory for re-calibration
Содержание TAI60
Страница 3: ...Page 2 U US SE E ...
Страница 7: ...Page 6 P PR RO OG GR RA AM MM MI IN NG G ...
Страница 14: ...Page 13 T TE EC CH HN NI IC CA AL L F FE EA AT TU UR RE ES S ...
Страница 18: ...Page 17 W WI IR RI IN NG G ...