Page 10
6. CONFIGURATION OF THE RELAY OUTPUTS (MENU « OUTPUTS »)
Each output is configured as alarm setpoint.
6.1. Configuration in mode setpoint « ALARM »
2 modes can be combined with 2 types of safeties:
Choice of the parameter to be watched « MEAS O »
U13
Selection of the measure to be watched.
IL1
…
MODE SINGLE WITH 1 SETPOINT , LOW SAFETY:
Setpoint
Contact closed
Value of the parameter
Contact open
The hysteresis is centered around the setpoint (0 to 15%).
MODE SINGLE WITH 1 SETPOINT , HIGH SAFETY:
Contact open
Value of the parameter
Contact closed
Setpoint
The hysteresis is centered around the setpoint (0 to 15%).
MODE WINDOW WITH 2 SETPOINTS , LOW SAFETY:
Setpoint 1
Setpoint 2
The hysteresis are centered around the setpoint (0 to 15%).
Contact open
Contact open
Contact
closed
Value of the parameter
MODE WINDOW WITH 2 SETPOINTS, HIGH SAFETY:
The hysteresis are centered around the setpoint (0 to 15%).
Value of the parameter
Contact closed
Contact closed
Contact
open
Setpoint 1
Setpoint 2