The series
Peca 5
offers you an extensive range of high accuracy program-
mable display centrals, IP 65 on front face. Each instrument is equipped
with a five 14mm high red digits display, whose brightness suits applica-
tions in industrial control rooms perfectly.
They allow display, control and transmission of data from any measurable
magnitudes of a single or 3-phase balanced network.
•
Peca 5
Types of networks :
single or 3-phase balanced with or without neutral
-Measurement of the network voltage, current and frequency
-Measurement of the power factor
-Measurement of the active, reactive and apparent power
-Measurement of the energies.
•
2 programmable voltage calibers : 150V or 500V
Un = 150 VAC and 500 VAC
Oversteppings 1.2 Un
•
2 programmable current calibers : 1A and 5A
In = 1.2A and 6A
Overstepping 1.2 In
Possibility of automatic calibration : 0-500V, 0-5A
•
Voltage overload :
Permanent : 750 V
During 10s : 1000 V
•
Current overload :
Permanent : 10A
During 10s : 50A
•
Frequency : 45 Hz to 65 Hz
•
Accuracy rating : 0.2 % voltage / current (at 25°C)
•
Measure cycle : 55 ms
•
Display : 3 magnitudes can be programmed on a display which is
accessible simply by pressing 1 key.
•
Accuracy rating : 0.5 % for powers (IEC 688-1)
•
Saving of the energies every 5 min.
•
Active energy accuracy cl 1 (IEC 61036).
1. INTRODUCTION
AVAILABLE OPTIONS
:
(specify on order)
Insulated analog output
: A
Active or passive current, or voltage output.
Programmable scale ratio with enlarging effect.
Relay output
: R or R4 : 2 or 4 relays :
Setpoint relays :
Mode setpoint or window.
Recording of alarms.
Time delay and hysteresis adjustable on each setpoint.
Alarm messages
Pulse output
Width of the pulses : 400 ms.
Maximum count rate : 1 pulse / second
Insulated digital output
: N
RS 485 2 wire, protocole
MODBUS-JBUS.
Bargraph
: (16 led display) : B
Allows a quick evaluation of the measured value
variations.
Programmable scale factor
3 bargraphs can be programmed
(1 for each displayed parameter).