p17
5.1 Functions which require pressing only 1 key :
a / Display of the min. value
b/ Display of the max. value
InF.
02.00
Measure
display
Alternate infor-
mation display
Minimum value
5. FUNCTIONS ACCESSIBLE DIRECTLY FROM
THE DISPLAY
SUP.
08.00
Measure
display
Alternate informa-
tion display
Maximum value
c / Display switching
(3 parameters can be displayed)
A long pressing (>3 s) on or allows switching to the next (or pre-
vious) parameter (a led indicates the selected parameter).
d / Deleting of the maximum and minimum values
There is one min. and one max. for each displayed parameter (except
energies).
M
the instrument reverts to measures display.
Reminder :
If no key is pressed during 20 s., the instrument will revert
to measure display.
Note :
An exit from mode programming with configuration saving will
reset the min. and max. values to zero.
CLr.M
Measure
display
Deleting of the recorded min. and max., and
revert to measure display
5.2 Functions which require pressing several keys
:
5.2.1 Automatic setting of the cut off
Automatic setting of the voltage cut off
Automatic setting of the current cut off
M
M
(Accessible according to the programmed access code)
The automatic voltage or current cut off setting is an operation that
will enforce the voltage or current to 0 for U (I) low values. Once the
menu is chosen, the instrument will measure the values on its inputs
and enforce display to 0 for values lower than the programmed cut-off
in percentage of the full scale. To eliminate these cut-offs, just go into
programming and programme a new cut-off value (current from 1.0% to
15% in manual caliber, from 0.2% to 15% of caliber 5A in auto caliber,
voltage from 1.0% to 20% in manual caliber, from 0.3% to 20% of cali-
ber 500V in auto caliber).
«
Cut.I
«
Cut.U
+ +
Voltage cut off setting Current cut off setting
5.2.2 Visualisation of the measure unit
Press and to see during 3 s the unit alternating with the
measure on the display.
Odd case of the energies :
in the case of the display of an energy, as soon as the energy unit
oversteps the unit of the maximum power, it will automatically appear
alternating with the display of the energy.
M
5.2.3 Display of the lower part of an energy counter
During the display of an energy, press
and to visualise the lower
part of that energy.
Eg. : Display
EA.in 34.56
103
Display of the lower part
0.007
Value of the energy :
34.56
kWh +
0.007
kWh = 34.567 kWh