0 to 5 Access to the automatic current and voltage cut off
6 to 9 No access
0 to 5 Access to the display and output simulations
6 to 9 No access
0 to 5 Access to the function zero reset of the energies
6 to 9 No access
0 to 5 Access to the quick entering of alarm setpoints
6 to 9 No access
p15
4.7 Reading of the configuration
Reading of the input parameters
Reading of the measure display parameters
Reading of the analog output parameters
(Option analog output)
Reading of the communication parameters
(Option digital output)
Reading of the alarm parameters
(Option 2 or 4 relays)
Reading of the safety parameters in case of
self-diagnosis error
Reading of the display programming
parameters (leds, bargraph led ...)
Reading of the instrument internal parameters
In each reading sub-menu, use keys and to move, and
to visualise parameters.
If no key is pressed during 20 s., the instrument will revert to
the measure display.
nuLL
nuLL
YES
=
nuLL
no
YES
=
=
nuLL
•
Deleting of the unsignificant zeros
Suppresses the unsignificant zeros on the left
hand side from the display.
Eg.
: Display value 0015
Display 0015
Display 15
Eg.
: Display value 00.15
Display 00.15
Display 0.15
no
YES
=
=
•
Display factor of the bargraph
(option bargraph only)
Value of the display parameter X corresponding to 0%
of the bargraph.
Value of the display parameter X corresponding to 100%
of the bargraph.
In case of overtepping the bargraph starts to blink.
d.bArX
F.bArX
rEAd
rEAd
InPut
diSPL
Out.MA
Out.U
JbuS
Pr.diS
About
or
Validation /
Vertical move
rELAY
SECU
4.8 Access code
An access code adjustable from 0000 to 9999 serves to protect the
meter and its setpoints from unauthorized programming, and to lock the
access to some functions.
0 0 0 0 Factory code
About
PECA5
n0
A0123
ProG
02.00
0Pt10.
Ar4--.
Err.
0000
CH.SUM
FC4E
Validation /
Vertical move
Type of instrument
Sub-menu
N° of the instrument
Programme version
Code of the ins-
talled options
Error code in case of
self-diagnosis error
Flash memory
check sum
X1 : - : No analog output
A : Analog output
X2 X3 : - - : No relay output
r- : Output 2 relays
r4 : Output 4 relays
X4 : - : No RS output
n : RS output
(.) : Decimal point still :
no bagraph
“.” : Decimal point lit :
option bargraph
1 2 3 4 5
.
XXXXX
00000
1 2 3 4 5
.
XXXXX
00000