p11
4.5.5 Choice of the CT ratio
Example
: For an installation with a CT of 5000 kA / 5 A
and
Pri.tc
5000.
SEc.tc
005.0
10 3
4.5.6 Choice of the VT ratio
Example
: For an installation with a VT of 400 kV / 110 V
and Display wit 1 cipher after the point
=> 400.0 for 110V
Pri.tP
400.0
SEc.tP
110.0
10 3
4.5.7 Choice of the operating mode
Receiver
Generator
This will set the direction of the current (180° rotation in the 4 quadrant
diagram).
•
Programming in mode receiver
ModE
rEC
GEn
Q+
Q-
P-
P+
P- Q+
Generating
capacitive
cos elec<0
cos math<0
cos elec>0
cos math<0
Generating
inductive
P- Q-
cos elec<0
cos math>0
Motor
capacitive
P+ Q-
Active energy counters
EA.in
and
Er.CAP
Active energy counters
EA.in
and
Er.ind
Active energy counters
EA.out
and
Er.ind
P displayed by the Peca 5 > 0
Q displayed by the Peca 5 > 0
Active energy counters
EA.out
and
Er.CAP
P+ Q+
Motor
inductive
cos elec>0
cos math>0
4.5.4 Choice of the voltage caliber
or only in manual
Features of the voltage input
Caliber
Display resolution
Input level
resolution
Accuracy
0 to 150 V
± 1 digit
10 bits
0.2% of m. range
0 to 500 V
± 1 digit
10 bits
0.2% of m. range
CALU
150
500
•
Programming in mode generator
Q+
Q-
P-
P+
P- Q+
Motor
capacitive
cos elec<0
cos math<0
cos elec>0
cos math<0
Motor
inductive
P- Q-
cos elec<0
cos math>0
Generating
capacitive
P+ Q-
Active energy counters
EA.in
and
Er.CAP
Active energy counters
EA.in
and
Er.ind
Active energy counters
EA.out
and
Er.ind
Active energy counters
EA.out
and
Er.CAP
P displayed by the Peca 5 > 0
Q displayed by the Peca 5 > 0
P+ Q+
Generating
inductive
cos elec>0
cos math>0
Note for the entering of the Pri.tc and Pri.tP :
The instrument will always try to display with the highest resolution.
eg. : for Pri.tP = 400.0, the display will be
for Pri.tP = 0400, the instrument will save the value Pri.tP = 400.0 and
we will have the same display in measure
likewise for Pri.tc = 0010, the instrument will save Pri.tc = 10.00 and in
measure we will have as display
The decimal point position is set once and for all on the configuration
saving (taking into account the display with the highest possible reso-
lution). It may in no case be modified in measure, that is to say after a
display of , if the input signal carries on increasing you will
have (display overstepping), and not
with
moving of the decimal point to the right.
Beware
: By pressing and
you can change the display resolu-
tion if you do not want to have a maximum resolution (
see p18
).
400.0
400.0
10.00
99.99
100.0
O.L