Voltages (line-to-line):
Currents:
U
L23
= 100.00 V, -90.00°
I
L2
= 2.5 A, -120.00°
I
L3
= 2.5 A, 120.00°
Name
Values
3PH (S)
20.00 MVA
3PH (P)
17.32 MW
3PH (Q)
0.00 Mvar
3PH Tan
0.00
3PH Cos
0.87
5.2.4 Frequency tracking and scaling
Measurement sampling can be set to the frequency tracking mode or to the fixed user-
defined frequency sampling mode. The benefit of frequency tracking is that the measurements are
within a pre-defined accuracy range even when the fundamental frequency of the power system
changes.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
85