Control settings
The control settings define the control model as well as the manual increasing and decreasing
commands from the HMI. The timing controls are here as well.
Table. 5.4.4 - 174. Control settings parameters.
Name
Description
Range
Step
Default
Description
Control mode
0: Auto
1: Manual
-
0: Auto
Displays the control mode: automatic or manual.
Max control
pulse length
0.000…1800.000s 0.005s 2.000s
Sets the maximum time the tap control's output
contact can be closed.
Min control
pulse length
0.000…1800.000s 0.005s 2.000s
Sets the minimum time the tap control's output
contact must be closed.
Min time
between pulses
0.000…1800.000s 0.005s 0.500s
Sets the minimum time between the separate
consecutive control commands.
Tap settings
The tap settings define the tap changer equipment properties and the connection for position
indication to the regulator. The tap settings also include indicators and measurements.
Table. 5.4.4 - 175. Tap settings parameters.
Name
Range
Step
Default
Description
Tap position
status
("Tap position
indication")
0: Select
1: mA internal
input 7
2: mA internal
input 8
3: mA external
input
4: Scaled input
5: Binary coded
inputs
6: mAIn1 (card 1)
7: mAIn2 (card 2)
8: BCD coded
inputs
-
0: Select
Selects the tap changer's input mode.
The "mA internal input x" options are the mA inputs
found in the RTD and mA input cards. The "mA external
input" option is an external ADAM mA input device
connected to the RS-458 port. The "Scaled input"
option in an input that has been scaled
at
Measurements
→
AI(mA, DI volt) scaling. The "BCD
coded inputs" and "Binary coded inputs" options refer to
the digital inputs. The "mAIn x" options are the mA
inputs included in the mA input card.
Tap position
indication
setting
0: Not selected
1: Set Ok
2: Wrong setting
3: Meas.Quality
Fault.
-
0: Not selected
Displays the health of tap position status setting.
Informs if the chosen measurement is not available or
the quality of the measurement is not good.
External mA
input channel
0: CH0
1: CH1
2: CH2
3: CH3
4: CH4
5: CH5
6: CH6
7: CH7
-
0: CH0
Selects the external mA input channel.
This setting is only visible when "mA external input" is
the selected input mode.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
281
Содержание AQ-T215
Страница 1: ...AQ T215 Transformer protection IED Instruction manual...
Страница 266: ...Figure 5 4 4 167 Connecting mA input to option card A AQ Q T215 T215 Instruction manual Version 2 04 265...
Страница 358: ...Figure 7 3 216 Example block scheme A AQ Q T215 T215 Instruction manual Version 2 04 357...
Страница 380: ...Figure 8 14 239 Panel cutout dimensions and device spacing A AQ Q T215 T215 Instruction manual Version 2 04 379...
Страница 409: ...10 Ordering information A AQ Q T215 T215 Instruction manual Version 2 04 408...