The selection of the AI channel in use is made with a setting parameter. In all possible input channel
variations the pre-fault condition is presented with a 20 ms averaged history value from -20 ms from
START or TRIP event.
Figure. 5.3.10 - 122. Selectable measurement magnitudes with 3LN+U4 VT connection.
Figure. 5.3.10 - 123. Selectable measurement magnitudes with 3LL+U4 VT connection (P-E voltages not available without
residual voltage).
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
167
Содержание AQ-T215