Tap position measured from resistance
Instead of mA measurement, RTD resistance is also an applicable option. To use RTD
measurement the position indication needs to be scaled in
Measurement
→
AI (mA, DI volt)
scaling (see the image below).
Figure. 5.4.4 - 171. Example scaling for tap position indication with RTD measurement.
A
AQ
Q-T215
-T215
Instruction manual
Version: 2.04
269