Name
Range
Step
Default
Description
Input value
2
-10
7
…10
7
0.001
1
The second input point in the mA output control curve.
Scaled mA
output
value 2
0.0000…24.0000mA 0.0001mA 0mA
The mA output value when the measured value is equal
to or greater than Input value 2.
Figure. 5.4.7 - 202. Example of the effects of mA output channel settings.
Table. 5.4.7 - 209. Hardware indications.
Name
Range Step
Description
Hardware in mA output channels 1...4 0: None
1: Slot A
2: Slot B
3: Slot C
4: Slot D
5: Slot E
6: Slot F
-
Indicates the option card slot where the mA output card is located.
Hardware in mA output channels 5...8
Table. 5.4.7 - 210. Measurement values reported by mA output cards.
Name
Range
Step
Description
mA in Channel 1
0.0000…24.0000mA 0.0001mA Displays the measured mA value of the selected input
channel.
mA in Channel 2
mA Out Channel Input
Magnitude now
-10
7
…10
7
0.001
Displays the input value of the selected mA output
channel at that moment.
mA Out Channel Outputs
now
0.0000…24.0000mA 0.0001mA Displays the output value of the selected mA output
channel at that moment.
5.4.8 Vector jump (Δφ; 78)
Distribution systems may include different kinds of distributed power generation sources, such as wind
farms and diesel or fuel generators. When a fault occurs in the distribution system, it is usually detected
and isolated by the protection system closest to the faulty point, resulting in the electrical power system
shutting dow either partially or completely. The remaining distributed generators try to deliver the
power to the part of the distribution system that has been disconnected from the grid, and usually an
overload condition can be expected. Under such overload conditions, it is normal to have a drop in
voltage and frequency. This overload results in the final system disconnection from the islanding
generator(s). The disconnection depends greatly on the ratio between the power generation and the
demand of the islanded system. When any power is supplied to a load only from distributed generators,
(due to the opening of the main switch), the situation is called an isolated island operation or an
islanded operation of the electrical distribution network.
A
AQ
Q-F213
-F213
Instruction manual