Mode
Description
4: Mag1 AND Mag2 AND
Mag3
All of the signals need to fulfill the pick-up condition. Each signal has their own pick-up
setting.
5: (Mag1 OR Mag2) AND
Mag3
Signals 1 OR 2 AND 3 need to fulfill the pick-up condition. Each signal has their own pick-up
setting.
The image below is an example of setting an analog comparison with three signals. The stage will trip if
Signal 1 or Signal 2 as well as Signal 3 fulfill the pick-up condition.
The settings for different comparisons are in the setting groups. This means that each signal parameter
can be changed by changing the setting group.