Page - 13
1.4.f Adjusting Water Flow Using ΔT (Delta-T)
The Delta-T is the temperature difference between the water temperatures entering and leaving the heat pump.
The equipment can be fine-tuned for maximum performance by balancing water flow rates to maintain an
ideal ∆T.
The adjustment procedure must be completed with the unit in heating mode.
l
Installed temperature ports are required to perform the following procedures.
l
These ports are typically located on the pool in and pool out water lines approximately six inches away from the
heat pump.
PLEASE NOTE -
l
The installation of temperature ports is required for all commercial applications.
l
The installation of temperature ports is strongly recommended for residential installations.
n
Temperature Port Kit (# STK0096)
Temperature Port
(Shown with Probe)
1. Adjust the thermostat to its lowest setting with the unit in
heating mode.
2. Deactivate the water filtration pump.
3. Confirm that the filters leading to the heat pump are clean.
4. Adjust the valves controlling water headed towards the heat
pump to the half-open position.
5. Adjust the valves controlling water leading away from the
heat pump to a fully open position.
6. Activate the pool water filtration pump.
7. Slowly raise the thermostat temperature until the heat pump
activates.
l
After a three-minute delay, the heat pump's compressor will start.
8. With the heat pump running, confirm the filtration pump is operating properly with adequate flow and no short
cycling.
9. Wait for water temperatures to stabilize (approximately 5 minutes).
12. Adjust valves in the following order using the temperature chart provided.
a. Adjust the valve that controls water exiting the heat pump until the correct temperature differential is
achieved. Match the temperature measured with a temperature probe to the chart.
b. Wait for water temperatures to stabilize. Then check the temperature again. Re-adjust the valve as needed.
13. Mark valves at these positions for future reference.
HEAT EXCHANGER
TYPE
MODEL
TEMPERATURE
Titanium ThermoLink
®
SQ120R
3° to 7° F
(1.7° C to 3.9° C)
Titanium ThermoLink
®
SQ125
3° to 7° F
(1.7° C to 3.9° C)
1
-
Ins
ta
lla
tion
Содержание HeatWave SuperQuiet SQ120R
Страница 2: ......
Страница 28: ...Page 24 Configure Call Flex Enter Installer Menus then proceed 1 Installation ...
Страница 33: ...Page 29 Configure for Smart Bus Controller Enter Installer Menus then proceed 1 Installation ...
Страница 36: ...Page 32 Configure 2 wire controller Enter Installer Menus then proceed 1 Installation ...
Страница 40: ...Page 36 1 Installation ...
Страница 41: ...Page 37 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation ...
Страница 42: ...Page 38 1 Installation ...
Страница 45: ...Page 41 1 Installation ...
Страница 47: ...Page 43 1 Installation ...
Страница 50: ...Page 46 1 Installation ...
Страница 53: ...Page 49 1 Installation ...
Страница 55: ...Page 51 1 Installation ...
Страница 58: ...Page 54 Turbo Boost 1 Installation ...
Страница 59: ...Page 55 Set Efficiency Mode to 24 Hour 1 Installation ...
Страница 60: ...Page 56 Set Efficiency Mode to Filtration Schedule 1 Installation ...
Страница 61: ...Page 57 1 Installation ...
Страница 63: ...Page 59 1 Installation ...
Страница 65: ...Page 61 1 Installation ...
Страница 84: ...Page 80 Model Number Example 3 Appendix ...
Страница 89: ......
Страница 144: ...Rev L 8 12 13 MASTERTEMP Pool and Spa Heater Installation and User s Guide 55 N TES ...