 450-DE/DM Hydronic Heating System Installation Manual

— Page F-1 —

 

The following information addresses the process of 

selecting an antifreeze and water mixture ratio that pro-

vides adequate freeze, boiling, and rust/anti-corrosive 

protection.  A 50/50 mixture ratio is recommended, 

which will result in a freeze point of approximately 

-28ºF and a boil point of  approximately 222ºF.

 

The following information should be utilized for the 

purpose of  clarifying some terms commonly associated 

with antifreeze.

Freeze Point and Burst Point:

 

Antifreeze lowers the freezing point of  any liquid, to 

which it has been added, by preventing the formation 

of  ice crystals; however, as the ambient temperature 

continues to decline, the water in the solution will at-

tempt to attain a solid state.   The point in which the 

water begins to solidify is termed the “Freeze Point.”  

Although the water in the solution has begun to freeze, 

producing a “slushy” consistency, the antifreeze in the 

solution will continue to combat the normal expansion 

of  the solution as it freezes.  The point in which the so-

lution can begin to expand, due to colder temperatures, 

is called the “Burst Point.”  Once the solution reaches 

the burst point, the potential is present for ruptured 

pipes to exist.  The burst point of  the antifreeze and 

water heating solution is dependent upon the brand of  

propylene glycol employed.

Boiling Point:

 

The Aqua-Hot utilizes the antifreeze and water heat-

ing solution as a transportation means for the heat 

produced from the internal processes.  The antifreeze 

absorbs the heat created until its boiling point is 

reached; it is at this point that the liquid turns to a gas 

and is expelled to prevent the heating system from 

overheating.  Each time the boiling point is reached, 

a loss of  efficiency occurs because the heat produced 

is expelled rather than utilized for the function of the 

heating system.  Therefore, a higher boiling point is 

desired in order to combat the loss of  efficiency, which 

allows the antifreeze to transport the heat created from 

the internal process throughout the motorhome where 

it can be utilized productively rather than dissipating 

due to its change from a liquid to a gas.

Rust and Anti-Corrosive Inhibitors:

 

Another major function of  antifreeze is to provide 

protection to the internal metal components of  the 

Aqua-Hot hydronic heating system from corrosion and 

rust.  Antifreeze is able to perform this function by the 

addition of  rust- and anti-corrosive inhibitors, which 

are designed specifically to activate in a water solution. 

Summary:

 

Antifreeze has three basic functions:  freeze protec-

tion, boil-over protection, and anti-corrosion and rust 

protection.  

 

Antifreeze is also primarily responsible for heat trans-

fer; however, antifreeze itself does not possess accept-

able heat transfer characteristics.  Therefore, as water is 

an excellent heat conductor, it is added to the mixture.  

A 50/50 solution of  propylene glycol antifreeze and 

water is recommended to provide the best perfor-

mance combination of  the aforementioned functions.  

If  excess propylene glycol exists within an antifreeze 

and water heating solution, the water’s heat absorption 

properties are compromised, which could ultimately 

inhibit the Aqua-Hot from providing adequate domes-

tic hot water and interior heating. 

 

Additionally, if  the antifreeze and water heating solu-

tion contains over 70 percent antifreeze, the freezing 

point is actually raised, resulting in less freeze protec-

tion.  Please reference the attached graphical represen-

tation regarding the percentage of  antifreeze to water 

and how it directly affects the solution’s freezing point.

Appendix F: Antifreeze Terms and Mixture Ratio

Содержание 450-DE Series

Страница 1: ...Installation Manual 2008 Aqua Hot Heating Systems Inc...

Страница 2: ...Requirements 10 Mounting the Heat Exchangers 11 Wiring the Heat Exchangers 13 Plumbing Requirements 14 Plumbing the Hydronic Heating System 15 Section 3 Thermostats Fresh Water Tank Thermostat Locatio...

Страница 3: ...Exhaust System 30 Section 9 Electronic Controller Wiring Electronic Controller Wiring 31 Wiring Harness Connection 32 Connecting the 12 Volt DC Power 33 Section 10 Purging the Systems Purging the Hyd...

Страница 4: ...reduces the time required to bring the tank to operating temperature for interior heat and continuous domestic hot water The Aqua Hot 450 DE also includes an engine preheat feature which provides an...

Страница 5: ...gal hr Heater Voltage Maximum Power Consumption 12 Volt DC 60 watts Electric Heating Element specifications 120 Volt AC 1650 watts Zone Heat Circulation Pump specifications 2 12 Volt DC 21 watts each...

Страница 6: ...ing Harness Harness Port VAC Access Panel Zone 2 Circulation Pump Zone 1 Circulation Pump Diesel Burner Interlock Switch Heating Zone 2 Outlet Port Heating Zone 1 Outlet Port Diesel Burner Controller...

Страница 7: ...ater Outlet Engine Preheat Outlet to engine Engine Preheat Inlet from engine Engine Preheat Circulation Pump Aqua Hot Hydronic Heating System Zone 1 Circulation Pump Zone 2 Circulation Pump Wiring Har...

Страница 8: ...8 66 Overall 30 35 Overall 1 19 Front of Flange 95 Typical 14 06 Cut Out 17 98 Cut Out 16 0 Center of Holes 14 30 Center of Holes 14 14 Center of Holes NOTE All measurements are in inches Motorhome Fl...

Страница 9: ...rom the Aqua Hot prior to placement into the installed mount ing tray Be sure to provide an adequate support system for the mounting tray if adequate support is not present a cross member will need to...

Страница 10: ...2008 Aqua Hot 450 DE DM Hydronic Heating System Installation Manual Side View Front View Rear View NOTE All measurements are in inches Top View Bottom View 450 DE DM Section 1 Aqua Hot Installation Fi...

Страница 11: ...g System Installation Manual Access Cover Fastener Access Cover Combustion Air Sleeve Mounting Tray Flange Mounting Tray Aqua Hot 450 D Section 1 Aqua Hot Installation Mounting Tray Flange Aqua Hot 45...

Страница 12: ...e 12 NOTE Avoid any dips and bends in the overflow tubing from the Aqua Hot to the expansion tank as air can become trapped in these dips and bends preventing the expan sion of the heating solution fr...

Страница 13: ...formation NOTE An accessory device is available for the Cozy Heat Ex changer for the purpose of redirecting the airflow from the heat exchanger Reference Figure 17 Mounting Requirements Sufficient ven...

Страница 14: ...ut out a 2 5 inch H x 10 inch W opening for each heat exchanger outlet and cold air return register Reference Figure 16 2 Mount each heat exchanger permanently into place Reference Figures 19 and 20 3...

Страница 15: ...2 Hydronic Heating System Vertical Mount Horizontal Mount Mounting Tab Figure 19 3 500 in 5 50 in 1 06 in 0 38 in 2 812 in 6 500 in 10 500 in 13 687 in 6 44 in 13 06 in 14 44 in NOTE Tolerances on th...

Страница 16: ...21 and Appendix A 4 Wire all heat exchangers in a zone in series Reference Figure 23 and Appendix A 5 Connect all electronic controller wires to the positive and negative leads of the heat exchanger R...

Страница 17: ...er in series on Heating Loop 1 Reference Figures 23 and 24 The fresh water tank bedroom and bathroom heat exchangers typically 3 must be plumbed together in series on Heating Loop 2 Reference Figures...

Страница 18: ...eat exchanger for both heating loops Reference Figures 24 and 26 Then connect each additional heat exchanger in the same arrangement low to high Reference Figure 23 4 Connect and clamp the inlet line...

Страница 19: ...onstant Tension Clamps Pex Insert Pex Insert Outlet Inlet 5 8 inch I D 3 4 inch O D 5 8 inch I D 3 4 inch O D Automotive Type Rubber Heater Hose Coupler 3 4 inch I D Automotive Type Rubber Heater Hose...

Страница 20: ...Loop Inlet Plumbing Port Constant Tension Clamps Hose Barb Fitting Rubber Hose Rubber Hose PEX Insert PEX Tube PEX Tube PEX Insert PEX Tube Hose Barb Fitting Hose Barb Fitting Heating Loop 1 Outlet P...

Страница 21: ...e a location for the thermostat based upon the previous location information 2 Once the thermostat has been completely wired permanently mount the thermostat in place Reference Figure 27 6 0 10 20 30...

Страница 22: ...o stats Room Thermostat Wiring 1 Run two 18 gauge wires from each room thermostat mounting location to the Aqua Hot s electronic con troller Reference Appendix A NOTE It is recommended that the wire n...

Страница 23: ...a water using fixture when computing pipe sizes NOTE As stated directly from the ANSI A119 2 NFPA 501C Standard on Recreation Vehicles 1993 Edition Piping Systems shall be sized to provide an adequat...

Страница 24: ...ndicate directional flow of domestic water To Hot Water Faucets Domestic Hot Water OUTLET Fresh Water Storage Tank Domestic Cold Water INLET To Cold Water Faucets Demand Pump AT Indicates options for...

Страница 25: ...e 31 4 45 5 00 275 2 33 275 150 4x 2 88 1 205 80 702 1 362 2 724 871 3x 3 595 5 4 3 1 5 4 3 1 5 4 3 1 Mounting Holes total of four Switch panel mounting requirements for Aqua Hot 450 DM All measuremen...

Страница 26: ...ctronic Controller Pin 1 Pin 3 Pin 5 to Diesel I to Diesel O to IND LT B6 Pin 4 to IND LT B3 Jumper Wire Jumper Wire NOTE The Engine Preheat and Electric Element switches possess Jumper Wires which ad...

Страница 27: ...Also be sure to reference the ANSI NFPA 1192 hand book for information regarding fuel distribution system specifications Fuel head pressure should not exceed 10 feet Refer ence Figure 35 Use a minimum...

Страница 28: ...ply protective shielding in areas where chafing may occur 450 DE DM 50 ft maximum distance 50 ft maximum distance Maximum Allowable Suction Height 7 feet Figure 36 3 Label both fuel lines indicating w...

Страница 29: ...VIEW of Fuel Filter Head Section 6 Fuel System Figure 38 Figure 37 Fuel Inlet Port Fuel Outlet Port Fuel Filter Input from Fuel Tank Fuel Pick Up Pipe reference Figure 27 Output to the Aqua Hot s Fue...

Страница 30: ...the potential for air traps Run both plumbing lines in areas where they cannot be pinched off or damaged during normal operating conditions Secure both plumbing lines where necessary and apply protec...

Страница 31: ...AL OUTLET PORT pressure outlet port Ideal Return Port T ToTTop side of the engine Hose Clamp Automotive Type Heater Hose Automotive Type Heater Hose Hose Clamp M NPT by Hose Barb To the Aqua Hot s Eng...

Страница 32: ...haust pipe cannot be longer than 20 feet The two black pipe exhaust fittings MUST be utilized with all installations Failure to conform could create a hazardous situation and will void the Aqua Hot s...

Страница 33: ...ve type exhaust piping and avoid bends if possible Reference Figure 41 A maximum of two 90 exhaust pipe bends are al lowed Reference Figure 41 Do not use galvanized pipe or fittings only black iron pi...

Страница 34: ...ting Tray Flange Exhaust Pipe Elbow Depth of Motorhome Bay Floor 450 DE DM 450 DE DM Figure 43 Installing the Exhaust System 1 Run the exhaust pipe to the driver s side of the vehicle and ensure that...

Страница 35: ...erefore be sure to use care when wiring these particular components to the electronic controller Each heating zone FAN circuit can supply up to 2 0 Amps of direct current This 12 Volt DC power source...

Страница 36: ...as much as 22 Amps of DC current Because the Aqua Hot is designed to shut down in the event that the DC voltage level drops too low to properly operate it is imperative that the proper wire gauge be d...

Страница 37: ...whether they are a power or a ground wire 3 Attach the VDC power wires onto the appropriate ter minal battery connections on the electronic controller Reference Appendix A 4 Connect both power and gro...

Страница 38: ...nd not through the top of the unit in order to avoid air traps Reference Figure 48 1 Open the Aqua Hot s drain valve located at the front of the heater Reference Figure 48 2 Connect a piece of inch PE...

Страница 39: ...from the ground source during the antifreeze and water heating solution filling procedure 5 Allow the circulation pump to operate for approxi mately 1 3 minutes in order to purge the corresponding hea...

Страница 40: ...he Aqua Hot from operating whenever the main access cover is not properly installed 2 Move the diesel burner switch to the ON position for approximately ten seconds ONLY then switch it OFF NOTE This p...

Страница 41: ...2008 Aqua Hot 450 DE DM Hydronic Heating System Installation Manual Appendix A Wiring Diagram Appendix A...

Страница 42: ...2008 Aqua Hot 450 DE DM Hydronic Heating System Installation Manual Page A 1 Appendix A Wiring Diagram...

Страница 43: ...Appendix B Appendix B Wire Gauge Information...

Страница 44: ...3 0 3 0 4 0 4 0 4 0 4 0 50 6 6 4 4 2 2 1 0 2 0 2 0 3 0 3 0 4 0 4 0 4 0 60 6 4 4 2 2 1 0 2 0 3 0 3 0 4 0 4 0 4 0 70 6 4 2 2 1 0 2 0 3 0 3 0 4 0 4 0 80 6 4 2 2 1 0 3 0 3 0 4 0 4 0 90 4 2 2 1 0 2 0 3 0 4...

Страница 45: ...Appendix C Appendix C Electronic Controller Features...

Страница 46: ...ery connection will ensure completion of the required 3 minute purge cycle of the Aqua Hot s diesel burner NOTE This illustration details the proper wiring requirements for the usage of the battery di...

Страница 47: ...he electronic controller use a thin straight nonmetallic object to access the button through the faceplate or by turning OFF the diesel burner switch on the interior switch panel for approximately 30...

Страница 48: ...Appendix D Appendix D Antifreeze Types...

Страница 49: ...ed specifically for winterizing appli cations only Although RV Marine antifreeze is often Generally Recognized as Safe by the FDA it should never be used in the Aqua Hot s Hydronic Heating System This...

Страница 50: ...Appendix E Appendix E Antifreeze Mixture Water Quality Recommendations...

Страница 51: ...ntifreeze with water suppliers of pre mixed antifreeze are responsible for the use of high quality distilled de ionized or soft water when preparing their antifreeze for sale Hard water possesses a hi...

Страница 52: ...Appendix F Appendix F Antifreeze Terms and Mixture Ratio...

Страница 53: ...oiling point is reached a loss of efficiency occurs because the heat produced is expelled rather than utilized for the function of the heating system Therefore a higher boiling point is desired in ord...

Страница 54: ...Installation Manual Page F 2 Appendix F Antifreeze Terms and Mixture Ratio 10 0 20 40 60 20 30 10 20 30 40 50 60 Freezing Point Temperature In Degrees Fahrenheit l o c y l G e n e l y p o r P f o e g...

Страница 55: ...15549 East Highway 52 Fort Lupton Colorado 80621 1 800 685 4298 Fax 303 857 9000 www aqua hot com...

Отзывы: