Chapter 3 

– Installation Guidelines 

 

 

 

Apprion Proprietary and Confidential

 

Page 7 

 

Chapter 3 

Installation Guidelines 

Overview 

The IONizer is intended to be installed as part of a complete wireless design solution.  IONizer’s can be 
mounted just about anywhere including high posts to achieve the best results. 

This chapter provides basic guidelines that pertain to each device. 

Basic Guidelines 

 

Cable routed through conduit has a maximum length restriction of 300 feet (91 meters). 

 

To comply with FCC RF exposure compliance requirements, the antennas used with the IONizer 
must be installed with a minimum separation distance of 25.26 cm from all persons, except the 
16 dBi Sector Antenna (Apprion P/N 89-1186-000) and the 19 dBi Directional Antenna (Apprion 
P/N 89-1187-000) which must be installed with a minimum separation distance of 48.97 cm 
from all persons. 

 

The 16 dBi Sector Antenna (Apprion P/N 89-1186-000) and the 19 dBi Directional Antenna 
(Apprion P/N 89-1187-000) are to be used for Point-to-Point operation only. 

 

Antennas must not be co-located or operated in conjunction with any other antenna transmitter 
unless separated by 20 cm or greater. 

 

Installation must be performed using authorized cables and/or connectors provided with the 
device or available from the manufacturer/distributor for use with this device. 

 

Changes or modification no expressly approved by the manufacturer or responsible party for the 
FCC compliance could void the user’s authority to operate this equipment. 

 

Maintenance is limited to the external enclosure surface and cable connections.  At no time 
should the unit be opened. 

 

IONizer’s mounted outdoors must be grounded with a connection of 1 OHM or less leading from 
the external grounding stud to earth ground.  When mounted indoors, the unit should be 
grounded to the building’s earth ground via a connection to the external grounding stud (if 
practical).  Follow all national, local, and plant electrical codes. 

 

IONizer’s must be properly grounded before making any other power and signal connections. 

 

Ionizer’s must always be grounded in a hazardous location as defined by the NEC or applicable 
local and country codes. 

Содержание IONizer 4200 Series

Страница 1: ...Apprion Proprietary and Confidential IONizer4200Series HardwareInstallationGuide Apprion Incorporated March 2009 ...

Страница 2: ...y and Confidential Revision History Date Document Revision Author s January 09 Version 1 David Cote February 09 Version 2 Updated antenna information David Cote March 09 Updated antenna co location information David Cote ...

Страница 3: ...7 Basic Guidelines 7 CHAPTER 4 MOUNTING METHODS 9 Overview 9 Pole Mounting 9 4200 Series 9 Requirements 9 Mounting Diagram 10 Wall Mounting 10 4200 Series 10 Requirements 10 Procedure 10 Sealing Antenna Connections 12 CHAPTER 5 GROUNDING AND CABLING THE IONIZER 13 Overview 13 Grounding 13 Grounding Procedures IONizer 4200 4220 13 IONizer 4200 15 Using 48V PoE from an iKIT 16 Using 24 VDC from an i...

Страница 4: ...Table of Contents Page iv Apprion Proprietary Confidential Directional Antennas 28 APPENDIX B IONIZER SPECIFICATIONS 29 Specifications 29 ...

Страница 5: ... This document is intended for use by the Apprion Services Group to aid in the installation of IONizer devices Apprion s Outsourced Documentation Team This document is intended to serve as input for other customer partner facing documentation that may be produced by Apprion s outsourced documentation team This document is Apprion PROPRIETARY AND CONFIDENTIAL Conventions Item Description Arial Bold...

Страница 6: ......

Страница 7: ...on Proprietary Confidential xv How to Use this Guide This guide provides detailed instructions on how to install and wire an IONizer device You should read ALL chapters for important information before attempting the installation ...

Страница 8: ......

Страница 9: ...gured to suit client requirements This guide deals with installation only Configuration instructions are provided in the IONizer Reference Guide IONizer 4200 Series Models IONizers in the 4200 Series are designed for use in Class I Division 2 hazardous locations as defined in the National Electrical Code NFPA 70 2005 particularly NEC Article 500 5 B 2 All wiring and conduit connections to the unit...

Страница 10: ...tennas used with the IONizer must be installed with a minimum separation distance of 25 26 cm from all persons except the 16 dBi Sector Antenna Apprion P N 89 1186 000 and the 19 dBi Directional Antenna Apprion P N 89 1187 000 which must be installed with a minimum separation distance of 48 97 cm from all persons The 16 dBi Sector Antenna Apprion P N 89 1186 000 and the 19 dBi Directional Antenna ...

Страница 11: ... protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed in accordance with the instruction guide may cause harmful interference to radio communications This equipment complies with Part 15 of the FCC rules Operation is subject to the following two conditions 1 This ...

Страница 12: ......

Страница 13: ...and connect an IONizer at your site Preparation The IONizers come packaged in specialized shipping containers each designed for the type of IONizer ordered Packaging Content Contents of the package depend on the IONizer purchased 4200 Series IONizer 4200 or 4220 Mounting Hardware 2 U bolts with associated hardware 4 wall anchor bolts Wire nuts for 24 VDC installation Manual Product Registration an...

Страница 14: ... installation Additional orderable accessories include Antenna s based on configuration Power over Ethernet PoE Injector with AC Power Cord Multiple length PoE cable Additional Ethernet cable Specialized mounting brackets and hardware Inspect the unit for any damage or missing items Contact your Apprion service representative for support Ensure that the nameplate on the IONizer your purchased indi...

Страница 15: ...be used for Point to Point operation only Antennas must not be co located or operated in conjunction with any other antenna transmitter unless separated by 20 cm or greater Installation must be performed using authorized cables and or connectors provided with the device or available from the manufacturer distributor for use with this device Changes or modification no expressly approved by the manu...

Страница 16: ......

Страница 17: ...device is mounted Pole Mounting 4200 Series Requirements 3 8 inch torque wrench inch socket head 2 5 16 U bolts supplied 4 Lock Washers supplied 4 Flat head washers and nuts supplied The IONizer can be mounted on vertical poles up to 2 inches in diameter using the U bolt hardware provided with the device The device must be mounted in the correct orientation with device connectors on the bottom fac...

Страница 18: ...ice is mounted Wall Mounting 4200 Series Requirements 4 inch anchor screws ELCO inch x 1 inch or equivalent 4 inch flat washers 3 8 inch power drill inch drill bit Phillips head screwdriver Procedure 1 Ensure that the surface is clean and free of loose debris 2 Use the device as a template using the mounting slots to mark screw locations on the mounting surface ...

Страница 19: ...owing diagram 3 Drill pilot holes using the recommended drill bit size 4 Mount the device to the surface using the anchor screws and flat washers per manufacturer s instructions The flat head washers should be between the unit mounting flange and the anchor screw head 5 You can also mount the IONizer on rails as shown ...

Страница 20: ...nections Antenna connections should be sealed to protect them from exterior harsh environments Use a self amalgamating poly isobutylene tape which over a period of time adheres to itself and forms a single amalgameted rubber molding that conforms to the shape of the item its covering Once the tape is in place for several hours the rubber molding is resistant to water and most solvents It remains s...

Страница 21: ... is 8 to 10 inch pounds The wire should be kept as short as possible while using grounding practices that are compliant with local codes and practices Note Ensure that the connection to a proper earth ground is made by certified and authorized personnel The ground must conform to all applicable codes and regulations The materials required to connect to a proper earth ground are defined by local co...

Страница 22: ...he IONizer Page 14 Apprion Proprietary Confidential The bottom of the IONizer may look slightly different depending on the specific model However the grounding stud on these models is always basically in the same location ...

Страница 23: ...ed inside the IONizer Each cable is terminated with an RJ45 connector In addition two additional cables are provided for the 24V option If the 24VDC option is not used the wires must be terminated and secured out of the way See Using 24 VDC from an iKIT in this chapter for more info The following diagram shows the recommended cabling for this device Note Two additional wires protrude from the same...

Страница 24: ...he conduit housing is also designed for easy disconnection for the conduit cabling system This housing contains two RJ45 couplers These couples are used to form a connection from the PoE source and the hardwired WAN and LAN cables Using 48V PoE from an iKIT The IONizer can also be connected to an Apprion iKIT which also supplies power and Ethernet The iKIT provides a convenient way to cable an ION...

Страница 25: ...roprietary and Confidential Page 17 Note This iKIT is designed for hazardous locations and has a stainless steel enclosure This iKIT must use conduit for ALL connections not shown in this diagram Refer to the specific iKIT Installation Guide ...

Страница 26: ...e made in the same area as the Ethernet cables to the IONizer inside the conduit housing These wires must be connected to 24 VDC cables coming from an iKIT or 24 VDC source Refer to the appropriate iKIT installation Guide for instructions on how to configure 24VDC inside the iKIT The use of wire nuts is suggested Termination of the 24 VDC wires can be done based on common industry practices per lo...

Страница 27: ...er distributor for use with this device Changes or modifications not expressly approved by the manufacturer or responsible party for this FCC compliance could void the user s authority to operate this equipment When installing authorized antennas make sure that the N Type connector is free of dirt and moisture The installer should properly ground themselves to minimize the chance of electrostatic ...

Страница 28: ...ed antennas for use with IONizer and provides specifications on each Omni Directional Antennas Dual Band Omni Standard 89 1584 000 Typical VSWR 2 0 1 max Impedance 50 Ohm Polarization Linear Input Power 10W Rated Wind Velocity 125 mph 56 m sec Operating Temperature 10 C min to 70 max Connector Type N Male Frequency 2400 5850 MHz Gain 2 dBi at 2400 MHz 4 dBi at 5725 MHz Horizontal Vertical BW 30 at...

Страница 29: ...Appendix A Approved Antennas Apprion Proprietary and Confidential Page 21 Vertical H Plane Horizontal E Plane ...

Страница 30: ...dance 50 Ohm Polarization Vertical Linear Input Power 2W Rated Wind Velocity 125 mph 56 m sec Operating Temperature 40 C min to 70 max Connector Type N Male Frequency 2400 2485 MHz Gain 7 dBi at 5150 5875 MHz 4 5 dBi at 2400 2500 MHz Horizontal Vertical BW 30 at 2 4GHz 15 at 5 GHz Weight 0 8 lbs 0 4kg Dimensions 27 x 0 6 685mm x 15mm ...

Страница 31: ...ically Polarized Omni 89 1183 000 Typical VSWR 1 5 1 Impedance 50 OHM Input Power 10 W Rated Wind Velocity 125 mph 56 m sec Operating Temperature 40 C min to 70 C max Connector Type N Male Frequency 2400 2485 MHz Gain 9dBi Vertical BW 14 Weight 0 8 lbs 0 4kg Dimensions 27 x 0 6 690mm x 15mm ...

Страница 32: ...Typical VSWR 2 0 1 Impedance 50 OHM Input Power 10W Rated Wind Velocity 125 mph 56 m sec Operating Temperature 30 C min to 65 C max Connector Type N Male Frequency 4900 5875 MHz Gain 10 dBi 3 dB Beamwidth Elevation 8 3 dB Beamwidth Azimuth Omnidirectional Weight 0 4 lbs 0 18 kg Dimensions 19 6 x 1 0 497 x 25 4mm H Plane ...

Страница 33: ...Appendix A Approved Antennas Apprion Proprietary and Confidential Page 25 E Plane ...

Страница 34: ...pical VSWR 1 5 1 Max Impedance 50 OHM Polarization Vertical Linear Input Power 50W Rated Wind Velocity 125 mph 56m sec Operating Temperature 40 C min to 70 max Connector Type N Male Frequency 2300 2700 MHz Gain 16 dBi Horizontal BW 120 Vertical BW 9 Mechanical Downtilt 30 Weight 6 65 lbs 3kg Dimensions 33 5 x 6 5 x 2 5 851 x 165 x 64 mm Pole Diameter 1 25mm to 2 50mm ...

Страница 35: ...8 1 max Impedance 50 OHM Polarization Vertical Linear Input Power 10 W Rated Wind Velocity 125 mph 56 m sec Operating Temperature 40 C min to 70 C max Connector Type N Male Frequency 5850 MHz Gain 16 dBi Horizontal BW 120 Vertical BW 6 Mechanical Downtilt 15 Weight 2 lbs 1 3 kg Dimensions 24 6 x 2 7 x 1 7 625 x 69 x 43 mm Pole Diameter 1 5 38mm to 3 5 89mm ...

Страница 36: ... OHM Polarization Vertical Linear Input Power 100W Rated Wind Velocity 125 mph 56 m sec Operating Temperature 40 C min to 70 C max Connector Type N Male Frequency 5850 MHz Gain 19 dBi Horizontal BW 16 Vertical BW 16 Cross Polarization 35 dB Front to Back 30 dB Bracket Tilt 45 Weight 17 6 oz 0 5 kg Dimensions 7 5 x 7 5 x 0 8 190 x 190 x 20 mm Pole Diameter 1 25mm to 2 5 64mm ...

Страница 37: ...p MII 10 100 Ethernet MACs On chip IEEE 1588 Hardware Assist IEEE 802 11 a b g mini PCI Modules Typical Expansion 12C SSP 2xHSS 2x921K UARTs USB2 Mechanical Size IONizer 4200 Series 11 00 inches 279 4mm x 11 00 inches 279 4mm x 4 00 inches 101 6mm Weight IONizer 4200 Series 6 lbs 2 7 kg 8 lbs 3 6 kg shipping weight Housing IONizer 4200 Series NEMA Type 4X IP67 Rated Aluminum Chassis Paint Urethane...

Страница 38: ... Division 2 CSA Listed to UL1604 for use in Class I Division 2 Zone2 Groups A B C D CSA Certified to CSA C22 2 No 213 for use in Class I Division 2 Zone 2 Groups A B C D EN60079 15 and EN50020 ATEX Zone 2 Category 3 Radio Certifications FCC U NII Part 15 EN 300 328 2 w R TTE Article 3 2 consideration EN 301 893 w R TTE Article 3 2 consideration EN 301 489 w R TTE Article 3 2 consideration European...