– 18 –
10/30/09 C000659B
H
K
DRAIN PAN
PVC PIPE
PVC RETURN BEND
NOTE:
'H' TO BE A MINIMUM OF
1/2" PLUS THE TOTAL SYSTEM
STATIC PRESSURE ("W.C.).
'K' TO EXCEED THE NEGATIVE
STATIC PRESSURE IN "W.C. OF
THE SECTION OF THE UNIT
WHERE THE DRAIN IS INSTALLED
AND DOUBLE WHEN SPACE
PERMITS.
DRAIN PLUG
PVC ELBOW
NIPPLE
PVC ADAPTER FITTING
90° LONG RADIUS
FPT x SLIP
NIPPLE
PVC ELBOW
90° LONG RADIUS
PVC PIPE
NIPPLE
(10/30/09 C000659B)
DRAIN
TO
DRAIN PANS UNDER A NEGATIVE PRESSURE
SUGGESTED P-TRAP DESIGN FOR CONDENSATE
DRAIN PAN
NOTE:
'G' TO BE A MINIMUM OF
1/2" PLUS THE TOTAL SYSTEM
STATIC PRESSURE ("W.C.).
'J' TO EXCEED THE POSITIVE
STATIC PRESSURE IN "W.C. OF
THE SECTION OF THE UNIT
WHERE THE DRAIN IS INSTALLED.
PVC ADAPTER FITTING
FPT x SLIP
NIPPLE
(10/30/09 C000659B)
DRAIN PANS UNDER A POSITIVE PRESSURE
SUGGESTED P-TRAP DESIGN FOR CONDENSATE
G
J
PVC PIPE
PVC RETURN BEND
DRAIN PLUG
PVC ELBOW
NIPPLE
90° LONG RADIUS
PVC ELBOW
90° LONG RADIUS
PVC PIPE
NIPPLE
DRAIN
TO