Table 8. Configuration parameters

 

Parameter 

Range of variability of the parameter and description 

Settings 

default

 

1: 

StYP

 type of 

output/input signal

 

0-20

 

current signal in the 0

÷

20 mA standard (full range 0

÷

21 mA)

 

0-20

 

4-20

 

current signal in the 4

÷

20 mA standard (full range 3.8

÷

21 mA)

 

0-10

 

voltage in the 0÷10 V standard (full range 0÷10.5 V)

 

2-10

 

voltage in the 2÷10 V standard (full range 1.9÷10.5 V)

 

2: 

dira

 type of the scale 

displayed

 

unit

 

direct in real units (mA or V)

 

unit

 

boto

 

programmable with parameters 3: 

rbot

 and 4:

 

rtoP

 

3: 

rbot

 

bottom of the indication 
range

 

/999

 ÷

 

9999

 

units – indication for 0/4 mA, 0/2 V - start of the output scale

 

0.0

 

 

4: 

rtoP

 

top of the indication 
range

 

/999

 ÷ 

9999

 units - indication for 20 mA, 10 V - end of the output scale

 

100.0

 

 

5: 

dot

 position of the 

point for the 
programmable scale 
(when parameter 2:

 

dira

 = 

boto

 )

 

0

 

no point

 

1

 

0.0

 )

 

0.0

 (0.0)

 

0.00

 (0.00)

 

0.000

 (0.000)

 

6:

 

FiLt

 degree of 

filtration

 

4

 ÷ 

15

 

digital filtration of measurements (response time) for

 

FiLt

 = 

4

 the response time is equal to approx. 0.3 s, for 

FiLt

 = 

15

 

approx. 1.3 s. A higher filtration rate means a smoother 
measurement value and a longer response time.

 

4

 

7:

 

ModE

 operation mode

 

in

 

input (measurement), mode also set using the 

[IN]

 button

 

 

out

 

output (setting), mode also set using the 

[OUT]

 button

 

8:

 

LiLo

 

lower setting limit

 

/999

 ÷

 

9999

 units, lower limit of the set value (parameter 11:

 

SEt

 ) when 

setting using the setter buttons

 

/9.99

 

9:

 

LiHi

 

upper setting limit

 

/999

 ÷

 9999

 units, upper limit of the set value (parameter 11:

 

SEt

 ) when 

setting using the setter buttons

 

99.99

 

10:

 

StEP

 

change increment

 

0

 ÷

 

2000

 units, change increment for set value (parameter 11: 

SEt

when 

setting using the setter buttons

 

0.10

 

11:

 

SEt

 

set value for the output 

lower setting limit: 0/4 mA, 0/2 V, parameter 3: 

rbot

 or 8:

 

LiLo

, upper setting 

limit: 20 mA, 10 V, parameter 4: 

rtoP

 or 9:

 

LiHi

, change increment: 10: 

StEP

 , 

applies to setting using buttons in the normal mode (chapter 6)

 

0.00

 

12:

 

riSE

  

soft start time

 

oFF 
1

 ÷

 

1800

 s 

duration of increasing slope (ramp) for the value 

 

oFF

 the 

function is off, description in chapter 9

 

oFF

 

off

 

13:

 

FALL

 

soft stop time

 

oFF 
1

 ÷

 

1800

 s 

duration of decreasing slope (ramp) for the value 

 

oFF

 

the 

function is off, description in chapter 9

 

oFF

 

off

 

14: 

cALo

 calibration of 

the zero 

moving the zero for measurements and setting 

-500

 ÷ 

500

 units

 

0.00

 

15: 

cALG

 gain

 

85.0

 ÷ 

115.0

 

calibration of inclination (sensitivity) for measurements and 
setting

 

100.0

 %

 

16: 

bLoc

 block of 

keyboard keys 

[IN]

[OUT] 

and the set value 

11: 

SET 

oFF

 

off (no blocks)

 

oFF

 

off

 

inou

 

block of keyboard keys 

[IN]

 and 

[OUT]

 is on

 

SEt

 

block of changes to set value changes 11 is on: 

SET

 

 

ALL

 

block of keyboard keys 

[IN]

 and 

[OUT]

 and value 11 is on: 

SET

 

 

Содержание AR911

Страница 1: ...ruction AR911 Setter analog signal measuring device Version 1 0 2 2013 03 20 APAR SALES OFFICE 05 090 Raszyn ul Ga czy skiego 6 Tel 48 22 101 27 31 48 22 853 49 30 E mail automatyka apar pl Website ww...

Страница 2: ...ER 3 3 CONTENTS OF THE SET 4 4 TECHNICAL DATA 4 5 DIMENSIONS OF THE ENCLOSUREAND DESCRIPTION OF CONNECTIONSAND ELEMENTS 5 6 BUTTON FUNCTIONS 6 7 RANGE OF INDICATIONS CHANGE OFAVALUE SET FOR AN OUTPUT...

Страница 3: ...measuring standard current and voltage signals analog output input setter or measuring device current 0 4 20 mA active output may not be supplied in a two wire current loop voltage 0 2 10 V the outpu...

Страница 4: ...mperature changes 0 005 of the input range C Output input response time 10 90 0 36 s output 0 32 1 3 s input programmable with parameter 6 FiLt A 7 segment LCD display without background illumination...

Страница 5: ...TION OF CONNECTIONS AND EXTERNAL ELEMENTS 1 Enclosure Enclosure type manual portable MBMO series Material ABS Enclosure dimensions 162 x 89 x 25 mm Protection rating IP43 IP20 on the connection side 2...

Страница 6: ...chapter 8 SET UP a stepwise limit change of the set value of the output signal upper value of the indication range 20 mA 10 V parameter 4 rtoP or setting range reduction 8 LiLo SET DOWN a stepwise li...

Страница 7: ...THE CONFIGURATION PARAMETERS All the configuration parameters of the device are stored in the non volatile EEPROM internal memory The parameters are set from the film keypad located on the front panel...

Страница 8: ...tput setting mode also set using the OUT button 8 LiLo lower setting limit 999 9999 units lower limit of the set value parameter 11 SEt when setting using the setter buttons 9 99 9 LiHi upper setting...

Страница 9: ...es are different than zero 12 riSE and 13 FALL a periodic triangular signal is generated on the outputs The limit values amplitudes of the output signal are equal to the limit values of the signal use...

Страница 10: ...errors one time and recurring Code Description of message the operating mode was initiated input output PoFF the calibrator was switched off manually or automatically due to low battery voltage CodE...

Страница 11: ...11 11 USER S NOTES...

Страница 12: ...12...

Отзывы: