APAR AR911 Скачать руководство пользователя страница 7

7

 

 

[UP]

 or 

[DOWN]

- moves to the next or previous parameter name 
- changes the value of the edited parameter

 

 

[ESC]

- cancels the change of the edited value (and displays the parameter name again) 
- displays again the set/measured value (after holding time > 1 s)

 

 
 

7. RANGE OF INDICATIONS. CHANGE OF A VALUE SET FOR AN OUTPUT

 

1.

  Depending on the setting of parameter 2:

 

dira

 (chapter 8, Table 8), the value of the set/measured signal may 

be presented directly in real values (mA or V, when 2:

 

dira

 = 

unit

 ) or may be calculated to any programmable 

range of indications suitable for the specific application (parameters 3: 

rbot

 and 4:

 

rtoP

, when 2:

 

dira

 = 

boto

 ).

 

2.

  In the set value display mode, when the [

UP

] or [

DOWN

] button is pressed, the value is changed by a preset 

step (parameter 10: 

StEP

 ). The changes of the output signal are proportional to the changes of the displayed 

value. When the 

[SET]

 and the 

[DOWN]

 buttons are pressed simultaneously, the output is immediately set to any 

permissible value in the range (0/4 mA, 0/2 V, 3: 

rbot

 or 8: 

LiLo

) while pressing the 

[SET]

 and the 

[UP] 

 buttons 

simultaneously causes the output to be set at the upper permissible value of the range (20 mA, 10 V, 4:

 

rtoP

 or 9: 

LiHi

 ).

 

Also, the output signal can be set in the parameter programming mode (parameter 11: 

SEt

 ). Moreover, it is 

possible to set a value outside of the indication range resulting from parameters 3:

 

rbot

 and 4: 

rtoP

. The value of 

this overload is equal to ±5% (in accordance with the full range of changes of the output signal described in 
chapter 4).

 

 
 
 

8. SETTING OF THE CONFIGURATION PARAMETERS

 

All the configuration parameters of the device are stored in the non-volatile EEPROM internal memory. 
The parameters are set from the film keypad located on the front panel of the device: 

 

from the set/measured value display mode go to the configuration menu (press 

[CONF]

 and hold it for more 

than 2 seconds) If parameter 18: 

Prot

 =

 

on

 (password protection is on) the display will show the 

message

CodE

, and then 

0000

 with the first digit blinking, use the buttons 

[UP]

 or 

[DOWN]

 to enter the 

password (default parameter 17: 

PASS

 = 

1111

 

), to move to successive items and to approve the code, use the 

[SET]

 button 

 

after you enter the configuration menu, the mnemonic names of the parameters are displayed ( 

StYP

 <->

 

dira

 <-> 

rbot

 <-> etc.); press the 

[UP] 

 button to go to the next parameter and the 

[DOWN]

 button to go to 

the previous parameter (a complete list of configuration parameters is presented in Table 8) 

 

 to change or view the value of the current parameter, press 

[SET]

 

 

use buttons 

[UP]

 or 

[DOWN]

 to change the value of the edited parameter; 

 

approve the changed value of the parameter by pressing 

[SET]

 or cancel it by pressing 

[ESC]

; then return to 

the parameter name display 

 

exit the configuration by long pressing (>1 s) the 

[ESC]

 button; otherwise, the system exits the menu 

automatically after approx. 2 minutes of idle condition 

In the event of indications different from the actual value of the input/output signal, the zero and the sensitivity of 
the sensor can be tuned to the specific signal: parameters 14:

 

cALo

 (zero) and 15: 

cALG

 (sensitivity). 

To restore the factory settings, when the device is switched on press button 

[CONF] 

 and hold it until the password 

menu appears (

CodE

), and then enter the following code  

0112

Содержание AR911

Страница 1: ...ruction AR911 Setter analog signal measuring device Version 1 0 2 2013 03 20 APAR SALES OFFICE 05 090 Raszyn ul Ga czy skiego 6 Tel 48 22 101 27 31 48 22 853 49 30 E mail automatyka apar pl Website ww...

Страница 2: ...ER 3 3 CONTENTS OF THE SET 4 4 TECHNICAL DATA 4 5 DIMENSIONS OF THE ENCLOSUREAND DESCRIPTION OF CONNECTIONSAND ELEMENTS 5 6 BUTTON FUNCTIONS 6 7 RANGE OF INDICATIONS CHANGE OFAVALUE SET FOR AN OUTPUT...

Страница 3: ...measuring standard current and voltage signals analog output input setter or measuring device current 0 4 20 mA active output may not be supplied in a two wire current loop voltage 0 2 10 V the outpu...

Страница 4: ...mperature changes 0 005 of the input range C Output input response time 10 90 0 36 s output 0 32 1 3 s input programmable with parameter 6 FiLt A 7 segment LCD display without background illumination...

Страница 5: ...TION OF CONNECTIONS AND EXTERNAL ELEMENTS 1 Enclosure Enclosure type manual portable MBMO series Material ABS Enclosure dimensions 162 x 89 x 25 mm Protection rating IP43 IP20 on the connection side 2...

Страница 6: ...chapter 8 SET UP a stepwise limit change of the set value of the output signal upper value of the indication range 20 mA 10 V parameter 4 rtoP or setting range reduction 8 LiLo SET DOWN a stepwise li...

Страница 7: ...THE CONFIGURATION PARAMETERS All the configuration parameters of the device are stored in the non volatile EEPROM internal memory The parameters are set from the film keypad located on the front panel...

Страница 8: ...tput setting mode also set using the OUT button 8 LiLo lower setting limit 999 9999 units lower limit of the set value parameter 11 SEt when setting using the setter buttons 9 99 9 LiHi upper setting...

Страница 9: ...es are different than zero 12 riSE and 13 FALL a periodic triangular signal is generated on the outputs The limit values amplitudes of the output signal are equal to the limit values of the signal use...

Страница 10: ...errors one time and recurring Code Description of message the operating mode was initiated input output PoFF the calibrator was switched off manually or automatically due to low battery voltage CodE...

Страница 11: ...11 11 USER S NOTES...