Figure 9.3. The principle of operation of outputs in the 

triangular wave generator mode

 (parameter 

 

riSE

 > 0, 

FALL

 > 0). 

 

 

10. MESSAGE AND ERROR SIGNALING. DIAGNOSTIC FUNCTIONS.

 

a) measurement and setting errors (diagnostic functions):

 

Code 

Possible causes of error

 

^^^^ 
____

 

- the permissible measurement range/set signal is exceeded from above ( 

^^^^

 ) or from below ( 

____

 ) 

- the signal that is connected is different than the one that is set in the configuration (chapter 8, parameter 1: 

StYP

 )

 

 

4.00

 

- the set value blinks - a break in the current loop circuit or a short-circuit in the voltage signal circuit. 
A message is shown when the expected value of the set signal is different from the measured real value by 
more than 1% of the total range of variability of the signal.

 

b) temporary messages and errors (one-time and recurring):

 

Code 

Description of message

 

----

 

 the operating mode was initiated (input/output),

 

PoFF

 

the calibrator was switched off (manually or automatically due to low battery voltage),

 

CodE

 

the mode for entering the password for access to the configuration parameters is entered (chapter 8),

 

Err

 

the password is invalid,

 

ConF

 

the parameter configuration menu was accessed,

 

bLoc

 

the value settings or the 

[IN]

 and 

[OUT]

 buttons block is switched on (using parameter 16:

 

bLoc

 , chapter 8)

 

rAMP

 

the value setting block is switched on due to the performance of the ramp function (chapter 9),

 

StAr

 

the soft start/stop function was started up manually (using the 

[SET] button),

 

StoP

 

the soft start/stop function was stopped manually (using the 

[SET] button),

 

LbAt

 

the voltage level of the power supply batteries is too low (the batteries must be charged using the enclosed 
power supply or the batteries must be changed to new ones),

 

SAUE

 

saving of factory parameter values (chapter 8).

 

 
 
 
 
 
 
 
 
 

Содержание AR911

Страница 1: ...ruction AR911 Setter analog signal measuring device Version 1 0 2 2013 03 20 APAR SALES OFFICE 05 090 Raszyn ul Ga czy skiego 6 Tel 48 22 101 27 31 48 22 853 49 30 E mail automatyka apar pl Website ww...

Страница 2: ...ER 3 3 CONTENTS OF THE SET 4 4 TECHNICAL DATA 4 5 DIMENSIONS OF THE ENCLOSUREAND DESCRIPTION OF CONNECTIONSAND ELEMENTS 5 6 BUTTON FUNCTIONS 6 7 RANGE OF INDICATIONS CHANGE OFAVALUE SET FOR AN OUTPUT...

Страница 3: ...measuring standard current and voltage signals analog output input setter or measuring device current 0 4 20 mA active output may not be supplied in a two wire current loop voltage 0 2 10 V the outpu...

Страница 4: ...mperature changes 0 005 of the input range C Output input response time 10 90 0 36 s output 0 32 1 3 s input programmable with parameter 6 FiLt A 7 segment LCD display without background illumination...

Страница 5: ...TION OF CONNECTIONS AND EXTERNAL ELEMENTS 1 Enclosure Enclosure type manual portable MBMO series Material ABS Enclosure dimensions 162 x 89 x 25 mm Protection rating IP43 IP20 on the connection side 2...

Страница 6: ...chapter 8 SET UP a stepwise limit change of the set value of the output signal upper value of the indication range 20 mA 10 V parameter 4 rtoP or setting range reduction 8 LiLo SET DOWN a stepwise li...

Страница 7: ...THE CONFIGURATION PARAMETERS All the configuration parameters of the device are stored in the non volatile EEPROM internal memory The parameters are set from the film keypad located on the front panel...

Страница 8: ...tput setting mode also set using the OUT button 8 LiLo lower setting limit 999 9999 units lower limit of the set value parameter 11 SEt when setting using the setter buttons 9 99 9 LiHi upper setting...

Страница 9: ...es are different than zero 12 riSE and 13 FALL a periodic triangular signal is generated on the outputs The limit values amplitudes of the output signal are equal to the limit values of the signal use...

Страница 10: ...errors one time and recurring Code Description of message the operating mode was initiated input output PoFF the calibrator was switched off manually or automatically due to low battery voltage CodE...

Страница 11: ...11 11 USER S NOTES...

Страница 12: ...12...

Отзывы: