Parameter setting

Alarm bit selection setting   

[Equipment parameter 1] 

If you set this parameter to “enabled,” the number of occupied input points is 

increased by one. When the alarm (ALM) indicator lamp lights, the alarm bit 

turns ON to indicate the alarm status to the controller.

Alarm detecting conditions are specified by equipment parameters 11, 12 and 14.

Alarm bit disabled

Alarm bit enabled 

Variable

Description

0

100

Factory setting: 0

Input 1 point 

Input 

n

n+1

Input 2 points

Input 1 Input 2

Input 1 point 

Input 

Offset address

Type

Offset address

Alarm

n

n+1

Input 2 points

Input 1 Input 2

Type

n+2

Alarm

[When enabled]

[When disabled]

This parameter is used to set an upper limit value of pressure detection input 0.

For both hysteresis mode and window comparator mode 

 Refer to equipment 

parameter 8.

Input 0 upper limit setting   

[Equipment parameter 2] 

B284SB-01-1KPP30, B284SB-02-1KPP30

B284SB-01-1KNP30, B284SB-02-1KNP30

Variable

Description

0 to 1000

0 to -100kPa

Factory setting: 600 (-60kPa)

Variable

Description

0 to 1000

0 to 1000kPa

Factory setting: 600 (600kPa)

Variable

Description

0 to 1000

0 to 100kPa

Factory setting: 600 (60kPa)

Variable

Description

0 to 1000

-100 to 100kPa

Factory setting: 600 (20kPa)

B284SB-01-1KLP30, B284SB-02-1KLP30

B284SB-01-1KPLP30, B284SB-02-1KPLP30

This parameter is used to set a lower limit value of pressure detection input 0.

For both hysteresis mode and window comparator mode 

 Refer to equipment 

parameter 8.

Input 0 lower limit setting   

[Equipment parameter 3] 

*This parameter cannot be set larger than the input 0 upper limit value (equipment parameter 2).

B284SB-01-1KPP30, B284SB-02-1KPP30

B284SB-01-1KNP30, B284SB-02-1KNP30

B284SB-01-1KLP30, B284SB-02-1KLP30

B284SB-01-1KPLP30, B284SB-02-1KPLP30

Variable

Description

0 to 1000

0 to 100kPa

Factory setting: 400 (40kPa)

Variable

Description

0 to 1000

-100 to 100kPa

Factory setting: 400 (-20kPa)

Variable

Description

0 to 1000

0 to -100kPa

Factory setting: 400 (-40kPa)

Variable

Description

0 to 1000

0 to 1000kPa

Factory setting: 400 (400kPa)

B284SB-02-1KPP30

B284SB-02-1KNP30

B284SB-02-1KLP30

B284SB-02-1KPLP30

Variable

Description

0 to 1000

0 to 100kPa

Factory setting: 400 (40kPa)

Variable

Description

0 to 1000

-100 to 100kPa

Factory setting: 400 (-20kPa)

Variable

Description

0 to 1000

0 to -100kPa

Factory setting: 400 (-40kPa)

Variable

Description

0 to 1000

0 to 1000kPa

Factory setting: 400 (400kPa)

Variable

Description

2

3

0

1

Variable

Description

0

1

Factory setting: 0

This parameter is used to set an upper limit value of pressure detection input 1. 

(For input 2 points type only)

For both hysteresis mode and window comparator mode 

 Refer to equipment 

parameter 8.

Input 1 upper limit setting   

[Equipment parameter 4] 

B284SB-02-1KPP30

B284SB-02-1KNP30

B284SB-02-1KLP30

B284SB-02-1KPLP30

Variable

Description

0 to 1000

0 to 100kPa

Factory setting: 600 (60kPa)

Variable

Description

0 to 1000

-100 to 100kPa

Factory setting: 600 (20kPa)

Variable

Description

0 to 1000

0 to -100kPa

Factory setting: 600 (-60kPa)

Variable

Description

0 to 1000

0 to 1000kPa

Factory setting: 600 (600kPa)

This parameter is used to set a lower limit value of pressure detection input 1. 

(For input 2 points type only)

For both hysteresis mode and window comparator mode 

 Refer to equipment 

parameter 8.

Input 1 lower limit setting   

[Equipment parameter 5] 

Hysteresis mode 

Window comparator mode

Input 0: Hysteresis mode, Input 1: Hysteresis mode

Input 0: Window comparator mode, Input 1: Hysteresis mode

Input 0: Hysteresis mode, Input 1: Window comparator mode

Input 0: Window comparator mode, Input 1: Window comparator mode

This parameter is used to set the hysteresis mode and/or window comparator 

mode of input 0 and input 1.

Operation mode selection   

[Equipment parameter 8] 

*For details, refer to page 11 to 12.

B284SB-01-1KPP30, B284SB-01-1KNP30, B284SB-01-1KLP30, B284SB-01-1KPLP30

B284SB-02-1KPP30, B284SB-02-1KNP30, B284SB-02-1KLP30, B284SB-02-1KPLP30

* This parameter cannot be set larger than the input 2 upper limit value (equipment parameter 4).

Factory setting: 0

Содержание ASLINKSENSOR

Страница 1: ...or serious injury A CAUTION indicates a potentially hazardous situation which if not handled correctly may result in personal injury or property damage If you set equipment parameter 1 alarm bit to en...

Страница 2: ...ction version Function version information is given on the lot label The design and contents of the lot label may vary depending on the product model and lot No Indication mode Model Functions Address...

Страница 3: ...should be connected to the DP DN terminal farthest from the AnyWireASLINK master unit Connect it correctly so as not to set the wrong polarity Connection with 2 wire non isolated terminals only Syste...

Страница 4: ...DC Notes on Combined Use of 4 Wire Isolated Terminal If the total length of the sections where all the DP DN 24V and 0V lines run in parallel in the power supply system is more than 50m connect an AS...

Страница 5: ...gth of the section where all the DP DN 24V and 0V lines run in parallel is more than 50m If the total length of the sections A B where all the DP DN 24V and 0V lines run in parallel is more than 50m 4...

Страница 6: ...parallel is more than 50m Filter representation in the drawing Local power supply branching If the total length of the section where all the DP DN 24V and 0V lines run in parallel is more than 50m In...

Страница 7: ...all be included in the total line length For address setting make sure that the specified number of transmission points is not exceeded If the specified number of transmission points is exceeded detec...

Страница 8: ...his unit to the AnyWireASLINK master unit A transmission signal is needed to write or read setting parameters Set parameters with the address writer with a transmission signal connected to the transmi...

Страница 9: ...scription 0 to 1000 0 to 100kPa Factory setting 400 40kPa Variable Description 0 to 1000 0 to 1000kPa Factory setting 400 400kPa B284SB 02 1KPP30 B284SB 02 1KNP30 B284SB 02 1KLP30 B284SB 02 1KPLP30 Va...

Страница 10: ...mit value The preset response time applies to both ON and OFF operations Input response time selection Equipment parameter 10 This parameter is used to set an alarm judgment monitoring time Alarm dete...

Страница 11: ...the master unit A bit corresponding to the status detail area turns ON depending on the contents of the alarm Hysteresis mode Equipment parameter 8 0 Positive logic Equipment parameter 9 0 Window com...

Страница 12: ...ime Time Pressure detected by sensor Input 1 point type Input 1 point type Input 1 point type Input 2 points type Hysteresis mode Equipment parameter 8 0 Positive logic Equipment parameter 9 0 Detecti...

Страница 13: ...plified replacement function does not work Check if the replacement slave unit is of the same type as that of the slave unit before the replacement Check if the function version for the replacement sl...

Страница 14: ...maximum transmission delay time is defined as this time word transmission cycle time Specifications 0 55 C 10 90 RH No condensation 25 75 C 10 90 RH No condensation Based on JIS B 3502 and IEC 61131...

Страница 15: ...s B284SB 01 1KPP30 B284SB 02 1KPP30 B284SB 01 1KNP30 B284SB 02 1KNP30 B284SB 01 1KLP30 B284SB 02 1KLP30 1kPa 0 1kPa 0 2kPa 0 1kPa B284SB 01 1KPLP30 B284SB 02 1KPLP30 Mounting panel 1 to 6mm Mounting b...

Страница 16: ...17 2018 2019 2020 UMA 14531AJ EN B284SB0 1K P30 16 16 Address Anywire Corporation Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Contact by mail Contact info_e anywire jp Contact by webs...

Отзывы: