background image

-BSK4117M**1K  4/9-

COSEL Co., Ltd. Type: EAC-06-472 Connection example

Power supply to the entire system

Local power supply/branching

DP

DN

24V
0V

LOAD

LINE

LG

24V

0V

L N FG

DP

DN

DP

DN

24V

0V

DP

DN

BT0

EAC-06-472

24V DC

stabilized 

power supply

Two-wire 

terminal

Four-wire 

terminal

24V

0V

24V

0V

PE

AnyWireASLINK master

If (A+B) of the side-by-side lines 
of DP, DN, 24V, or 0V exceeds 
the total length of 50m

DP

DN

24V
0V

LG

24V

0V

L N FG

DP

DN

24V

0V

DP

DN

DP

DN

24V

0V

DP

DN

BT0

24V DC

stabilized 

power supply

If any of the side-by-side lines 
of DP, DN, 24V, or 0V exceeds 
the total length of 50m

Two-wire 

terminal

DP

DN

Two-wire 

terminal

DP

DN

Two-wire 

terminal

Four-wire 

terminal

DP

DN

24V

0V

Four-wire 

terminal

Four-wire 

terminal

DP

DN

24V

0V

Four-wire 

terminal

DP

DN

24V

0V

Four-wire 

terminal

24V

0V

24V

0V

PE

AnyWireASLINK master

24V

0V

L

N

FG

24V DC

stabilized 

power supply

24V

0V

24V

0V

PE

DP

DN

24V

0V

Four-wire 

terminal

DP

DN

24V

0V

Four-wire 

terminal

A

B

General-purpose 
power supply filter
(Use if necessary)

General-purpose 
power supply filter
(Use if necessary)

General-purpose 
power supply filter
(Use if necessary)

LOAD

LINE

EAC-06-472

LOAD

LINE

EAC-06-472

(The figure is an explanatory schematic. 

Adjust the actual terminal layout to meet each device.)

When using this filter, 
please be careful of the 
positions of LOAD and 
LINE.

When using this filter, 
please be careful of the 
positions of LOAD and 
LINE.

If any of the side-by-side lines 
of DP, DN, 24V, or 0V exceeds 
the total length of 50m

Содержание ASLINKSENSOR BS-K4117-M 1K Series

Страница 1: ...circuit or similar problem in the hybrid unit including the output unit and the output circuit may result in smoke generation or fire An external safety device such as a fuse must be installed System power supply Use a stabilized 24V DC power supply Use of a non stabilized power supply may cause problems with the system Separately route high voltage and power cables Although the AnyWireASLINK has ...

Страница 2: ...for the AnyWireASLINK according to the load current This Products Guide describes a two wire non isolated terminal If the load current is small using a two wire non isolated terminal allows for achieving simplified wiring without a local power supply If you are prioritizing the sites of concentrated loads or the number of units connected hybridization with a four wire isolated terminal which suppo...

Страница 3: ... EAC 06 472 MAX 6A 24V DC Model Type Allowable power current Filter allowable power current Insert the ASLINK filter Type ANF 01 regardless of installation method and distance when complying with CE Standard General purpose power supply filter Use if necessary General purpose power supply filter Use if necessary POWER IN SLAVE The figure is an explanatory schematic Adjust the actual terminal layou...

Страница 4: ...re terminal Four wire terminal DP DN 24V 0V Four wire terminal Four wire terminal DP DN 24V 0V Four wire terminal DP DN 24V 0V Four wire terminal 24V 0V 24V 0V PE AnyWireASLINK master 24V 0V L N FG 24V DC stabilized power supply 24V 0V 24V 0V PE DP DN 24V 0V Four wire terminal DP DN 24V 0V Four wire terminal A B General purpose power supply filter Use if necessary General purpose power supply filt...

Страница 5: ...and then hitch the hook C to fix the cover Insert the body clamp into the hole of the cover and crimp them with a dedicated tool For the LP4 WW 10P perform crimping with pin 1 for DN pin 2 for DP and pins 3 and 4 empty After crimping check that the hooks to are securely engaged With cover mounted Check that the hooks and are engaged Installation Location Precautions for Use If you expect you will ...

Страница 6: ...etting is changed in the WRITE mode the setting is reflected after the system is re started up When setting is changed in the DIRECT WRITE mode the setting is reflected at the time when the writing is completed If this unit is included in a parallel arrangement use the remote head ARW RH together and ensure that writing is not performed to terminals not intended Make sure to use a 24V DC stabilize...

Страница 7: ...timer ON delay timer enabled OFF delay timer enabled Address writer ARW 04 ARW 03 Parameter 10 Default 0 Set the ON delay timer OFF delay timer 0 255 Default 0 Address writer ARW 04 ARW 03 Parameter 11 Normally open Normally close setting Variable Details 0 Normally open ON with work present Set the normally open normally close 1 Normally close ON with work absent Alarm value Hi setting Alarm valu...

Страница 8: ...as shown below ASLINKSENSOR is not connected to an AnyWireASLINK system Power supply for the AnyWireASLINK system itself is not turned on Directly connected to 24 0V power supply The ASLINKSENSOR maintains the address number 255 default setting The ASLINKSENSOR has an address redundant with another unit Transmission signal level reduction has been detected The sensing level has been reduced Confir...

Страница 9: ...2017 UMA 16717A EN Outside Dimensions Unit mm BS K4117 M18 1K BS K4117 M12 1K BS K4117 M30 1K Transmission cable Oil resistant flex resistant type φ29 24 1000 15 5 35 4 10 17 M18X1 Red DP Black DN Transmission cable Oil resistant flex resistant type Red DP Black DN φ21 17 35 5 3 10 15 4 1000 11 M12X1 10 5 Red DP Black DN M30X1 5 43 36 φ42 17 6 1000 Transmission cable Oil resistant flex resistant t...

Отзывы: