-BSK4117M**1K  8/9-

[Specifications]

-10 - 60°C, 10 - 90%RH (No condensation)

Ambient temperature/humidity for use

-25 - 75°C, 10 - 90%RH (No condensation)

Ambient temperature/humidity for storage

No corrosive gas

General Specifications

Atmosphere for use

0 to 2000m

Altitude of use *

1

2 or less

Pollution level *

2

Transmission specifications

Frame/bit synchronization method

Synchronization method

DC power supply superimposed total frame/cyclic method

Transmission method

Voltage 24V DC +15% to -10% (21.6 to 27.6V DC

Ripple of 0.5Vp-p max.

Power supply voltage 

for use

Dedicated protocol

Transmission procedure

Bus type 

(Multi-drop method, T-branch method, Tree branch method)

Connection mode

512 max. (IN: 256, OUT: 256)

Number of connection points

Up to 128 units

Number of units connected
RAS feature

Individual specifications

Consumption current

Number of occupied points

Mass
(This product/Cable)

Electromagnetic induction detection

Detection method

Shield type

Shield presence/absence

Non-magnetic metal/Magnetic metal

Detection target *

3

Standard detection objects

Depends on parameter setting
Max. 10ms

Detection distance

Hysteresis
Response time *

4

Detection distance at 23°C

Impact from 
temperature

Impact from voltage

(At ambient temperature 
of 23°C)

M18: 5mm (max.)

M18: Aluminum 18×18×3mm

M12: Approx. 37g
M18: Approx. 49g

M30: Approx. 105g

Mass
(Nuts/Washer)

M12: Approx. 8g
M18: Approx. 19g

M30: Approx. 41g

M12: Aluminum 12×12×3mm M30: Aluminum 30×30×3mm

M12: 2mm (max.)

M30: 10mm (max.)

Stable detection 
distance

M18: 0 to 4.5mm

M12: 0 to 1.6mm

M30: 0 to 9.0mm

M12: Within ±20%
M18: Within ±10%

M30: Within ±10%

IP67

Protective structure

Supplied via AnyWireASLINK transmission signal (DP, DN)
M12: 13mA
M18: 13mA

M30: 13mA

One-point input

*1 Do not use or store the AnyWireASLINK device in an environment pressurized equal to 

or higher than the atmospheric pressure at an altitude of 0m. Doing so could cause a 
malfunction.

*2 Index that indicates the occurrence of conductive material in the environment where 

the device is used.
Contamination level 2 indicates that only non-conductive contamination occurs.
However, incidental condensation could create temporary conductivity in this 
environment.

*3 The detection distance depends on the material.

*4 Time from when ON or OFF is detected until the transmission signal is transmitted.

The time combining this time and the transmission 2 cycle time is the transmission 
delay time.

Transmission line disconnection detection, 
transmission line short-circuit detection, 
transmission power supply reduction detection,
ID redundancy, ID not set detection

Within ±1% of the detection distance with the 
AnyWireASLINK master supplied power voltage 
within range of 27.6 to 21.6V

LINK

IN

ALM

Cause

Measures

Off

Off

Off

On

Off

Off

Flashing

(0.5 seconds 
alternately)

Off

Flashing

(0.5 seconds 
alternately)

Flashing

(On for 

0.2 seconds,

off for 

1.0 seconds)

Flashing

On

[Troubleshooting]

If the followings are displayed on the LEDs of this product, take 
measures as shown below.

- ASLINKSENSOR is 

not connected to an 

AnyWireASLINK 

system.

- Power supply for the 

AnyWireASLINK 

system itself is not 

turned on.

- Directly connected to 

24-0V power supply.

- The ASLINKSENSOR 

maintains the 

address number 255 

(default setting).

- The ASLINKSENSOR 

has an address 

redundant with 

another unit.

- Transmission signal 

level reduction has 

been detected.

- The sensing level 

has been reduced.

- Confirm that there is no 

disconnection between the 

ASLINKSENSOR and the 

AnyWireASLINK system, and recover 

the connection.

- Confirm the power status of the 

AnyWireASLINK system, and turn on 

the power.

- Re-connect to the AnyWireASLINK 

system.

- Set any address number other than 

255.

- Look for the other unit which has the 

same error indication, and set any 

address number different from it.

- Decrease the number of units 

connected to the same 

AnyWireASLINK system.

- Shorten the transmission line 

between the ASLINKSENSOR and 

the master unit.

- Confirm the ASLINKSENSOR status, 

adjust the position, and clean the 

detection surface.

Flashing

(0.1 seconds 
alternately)

Flashing

- Teaching is not 

normally operated.

- Make sure to perform teaching 

operation again.

Take measures as follows in the following case.

Symptom

Measures

Detection cannot be 
performed.

Setting cannot be 
performed with 
the address writer.

Indication

Cause

Measures

[E-0303]

When the following error is indicated on the address writer, take 

measures as shown below.

The set parameter is incorrect.

Check the parameter and set the correct 

parameter.

- Is the detected metal in the appropriate location?
   

 Make adjustments so that the detected metal is within an appropriate range 

from the ASLINKSENSOR detection surface.

- Is wiring correct?
   

 Confirm that the ASLINKSENSOR transmission line is correctly connected 

to the AnyWireASLINK transmission line (DP, DN).

- Are the AnyWireASLINK master unit and slave unit powered by a power supply 

with the appropriate capacity?

   

 Confirm the power supply.

- Did you perform teaching?
   

 Perform teaching settings with the work that is actually detected.

- Are you using within the rated detection range?
   

 Use within the rated range.

- Is wiring correct?
   

 Reconfirm the ASLINKSENSOR transmission line connection.

- Is power fed to the AnyWireASLINK system?
   

 Confirm the power supply.

- Is the set parameter correct?
   

 Check the parameter and set the correct parameter.

[Parameters and items]

Parameter

Default

variable

Variable

Details

[01.]

M12 : 18
M18 : 24
M30 : 26

M12 : 19
M18 : 25
M30 : 27

Set the threshold of the sensing level 
to judge presence/absence of detection.

0 - 100%

Threshold

[02.]

5

Set change amount of sensing level 
required to turn detection state ON to OFF.

0 - 100%

Hysteresis
[03.]

80

Set an upper limit for the alarm 
judgment value.

0 - 100%

Alarm value Hi
[04.]

Set a lower limit for the alarm 
judgment value.

0 - 100%

Alarm value Lo

[05.]

50

Set a monitor time for the alarm 
judgment value. (1 = 100ms)

3-255

Alarm value

monitor time
[06.]

0

Normally open

Normally close

0

Normally open/

Normally close
[07.]

0

Simple mode

Normal mode

0

Operation 

mode
[10.]

0

Delay timer disabled

ON delay timer

Delay timer

ON/OFF

[11.]

0 - 255

Set the delay time. (1 = 10ms)

0

Delay timer 

value

1

1

0
1

OFF delay timer

ON/OFF delay timer

2

3

Содержание ASLINKSENSOR BS-K4117-M 1K Series

Страница 1: ...circuit or similar problem in the hybrid unit including the output unit and the output circuit may result in smoke generation or fire An external safety device such as a fuse must be installed System power supply Use a stabilized 24V DC power supply Use of a non stabilized power supply may cause problems with the system Separately route high voltage and power cables Although the AnyWireASLINK has ...

Страница 2: ...for the AnyWireASLINK according to the load current This Products Guide describes a two wire non isolated terminal If the load current is small using a two wire non isolated terminal allows for achieving simplified wiring without a local power supply If you are prioritizing the sites of concentrated loads or the number of units connected hybridization with a four wire isolated terminal which suppo...

Страница 3: ... EAC 06 472 MAX 6A 24V DC Model Type Allowable power current Filter allowable power current Insert the ASLINK filter Type ANF 01 regardless of installation method and distance when complying with CE Standard General purpose power supply filter Use if necessary General purpose power supply filter Use if necessary POWER IN SLAVE The figure is an explanatory schematic Adjust the actual terminal layou...

Страница 4: ...re terminal Four wire terminal DP DN 24V 0V Four wire terminal Four wire terminal DP DN 24V 0V Four wire terminal DP DN 24V 0V Four wire terminal 24V 0V 24V 0V PE AnyWireASLINK master 24V 0V L N FG 24V DC stabilized power supply 24V 0V 24V 0V PE DP DN 24V 0V Four wire terminal DP DN 24V 0V Four wire terminal A B General purpose power supply filter Use if necessary General purpose power supply filt...

Страница 5: ...and then hitch the hook C to fix the cover Insert the body clamp into the hole of the cover and crimp them with a dedicated tool For the LP4 WW 10P perform crimping with pin 1 for DN pin 2 for DP and pins 3 and 4 empty After crimping check that the hooks to are securely engaged With cover mounted Check that the hooks and are engaged Installation Location Precautions for Use If you expect you will ...

Страница 6: ...etting is changed in the WRITE mode the setting is reflected after the system is re started up When setting is changed in the DIRECT WRITE mode the setting is reflected at the time when the writing is completed If this unit is included in a parallel arrangement use the remote head ARW RH together and ensure that writing is not performed to terminals not intended Make sure to use a 24V DC stabilize...

Страница 7: ...timer ON delay timer enabled OFF delay timer enabled Address writer ARW 04 ARW 03 Parameter 10 Default 0 Set the ON delay timer OFF delay timer 0 255 Default 0 Address writer ARW 04 ARW 03 Parameter 11 Normally open Normally close setting Variable Details 0 Normally open ON with work present Set the normally open normally close 1 Normally close ON with work absent Alarm value Hi setting Alarm valu...

Страница 8: ...as shown below ASLINKSENSOR is not connected to an AnyWireASLINK system Power supply for the AnyWireASLINK system itself is not turned on Directly connected to 24 0V power supply The ASLINKSENSOR maintains the address number 255 default setting The ASLINKSENSOR has an address redundant with another unit Transmission signal level reduction has been detected The sensing level has been reduced Confir...

Страница 9: ...2017 UMA 16717A EN Outside Dimensions Unit mm BS K4117 M18 1K BS K4117 M12 1K BS K4117 M30 1K Transmission cable Oil resistant flex resistant type φ29 24 1000 15 5 35 4 10 17 M18X1 Red DP Black DN Transmission cable Oil resistant flex resistant type Red DP Black DN φ21 17 35 5 3 10 15 4 1000 11 M12X1 10 5 Red DP Black DN M30X1 5 43 36 φ42 17 6 1000 Transmission cable Oil resistant flex resistant t...

Отзывы: