-BSK4117M**1K 8/9-
[Specifications]
-10 - 60°C, 10 - 90%RH (No condensation)
Ambient temperature/humidity for use
-25 - 75°C, 10 - 90%RH (No condensation)
Ambient temperature/humidity for storage
No corrosive gas
■
General Specifications
Atmosphere for use
0 to 2000m
Altitude of use *
1
2 or less
Pollution level *
2
■
Transmission specifications
Frame/bit synchronization method
Synchronization method
DC power supply superimposed total frame/cyclic method
Transmission method
Voltage 24V DC +15% to -10% (21.6 to 27.6V DC
Ripple of 0.5Vp-p max.
Power supply voltage
for use
Dedicated protocol
Transmission procedure
Bus type
(Multi-drop method, T-branch method, Tree branch method)
Connection mode
512 max. (IN: 256, OUT: 256)
Number of connection points
Up to 128 units
Number of units connected
RAS feature
■
Individual specifications
Consumption current
Number of occupied points
Mass
(This product/Cable)
Electromagnetic induction detection
Detection method
Shield type
Shield presence/absence
Non-magnetic metal/Magnetic metal
Detection target *
3
Standard detection objects
Depends on parameter setting
Max. 10ms
Detection distance
Hysteresis
Response time *
4
Detection distance at 23°C
Impact from
temperature
Impact from voltage
(At ambient temperature
of 23°C)
M18: 5mm (max.)
M18: Aluminum 18×18×3mm
M12: Approx. 37g
M18: Approx. 49g
M30: Approx. 105g
Mass
(Nuts/Washer)
M12: Approx. 8g
M18: Approx. 19g
M30: Approx. 41g
M12: Aluminum 12×12×3mm M30: Aluminum 30×30×3mm
M12: 2mm (max.)
M30: 10mm (max.)
Stable detection
distance
M18: 0 to 4.5mm
M12: 0 to 1.6mm
M30: 0 to 9.0mm
M12: Within ±20%
M18: Within ±10%
M30: Within ±10%
IP67
Protective structure
Supplied via AnyWireASLINK transmission signal (DP, DN)
M12: 13mA
M18: 13mA
M30: 13mA
One-point input
*1 Do not use or store the AnyWireASLINK device in an environment pressurized equal to
or higher than the atmospheric pressure at an altitude of 0m. Doing so could cause a
malfunction.
*2 Index that indicates the occurrence of conductive material in the environment where
the device is used.
Contamination level 2 indicates that only non-conductive contamination occurs.
However, incidental condensation could create temporary conductivity in this
environment.
*3 The detection distance depends on the material.
*4 Time from when ON or OFF is detected until the transmission signal is transmitted.
The time combining this time and the transmission 2 cycle time is the transmission
delay time.
Transmission line disconnection detection,
transmission line short-circuit detection,
transmission power supply reduction detection,
ID redundancy, ID not set detection
Within ±1% of the detection distance with the
AnyWireASLINK master supplied power voltage
within range of 27.6 to 21.6V
LINK
IN
ALM
Cause
Measures
○
○
○
Off
Off
Off
●
On
○
Off
○
Off
◎
Flashing
(0.5 seconds
alternately)
○
Off
◎
Flashing
(0.5 seconds
alternately)
-
-
◎
Flashing
(On for
0.2 seconds,
off for
1.0 seconds)
◎
-
●
Flashing
On
[Troubleshooting]
If the followings are displayed on the LEDs of this product, take
measures as shown below.
- ASLINKSENSOR is
not connected to an
AnyWireASLINK
system.
- Power supply for the
AnyWireASLINK
system itself is not
turned on.
- Directly connected to
24-0V power supply.
- The ASLINKSENSOR
maintains the
address number 255
(default setting).
- The ASLINKSENSOR
has an address
redundant with
another unit.
- Transmission signal
level reduction has
been detected.
- The sensing level
has been reduced.
- Confirm that there is no
disconnection between the
ASLINKSENSOR and the
AnyWireASLINK system, and recover
the connection.
- Confirm the power status of the
AnyWireASLINK system, and turn on
the power.
- Re-connect to the AnyWireASLINK
system.
- Set any address number other than
255.
- Look for the other unit which has the
same error indication, and set any
address number different from it.
- Decrease the number of units
connected to the same
AnyWireASLINK system.
- Shorten the transmission line
between the ASLINKSENSOR and
the master unit.
- Confirm the ASLINKSENSOR status,
adjust the position, and clean the
detection surface.
◎
-
◎
Flashing
(0.1 seconds
alternately)
Flashing
- Teaching is not
normally operated.
- Make sure to perform teaching
operation again.
Take measures as follows in the following case.
Symptom
Measures
Detection cannot be
performed.
Setting cannot be
performed with
the address writer.
Indication
Cause
Measures
[E-0303]
When the following error is indicated on the address writer, take
measures as shown below.
The set parameter is incorrect.
Check the parameter and set the correct
parameter.
- Is the detected metal in the appropriate location?
→
Make adjustments so that the detected metal is within an appropriate range
from the ASLINKSENSOR detection surface.
- Is wiring correct?
→
Confirm that the ASLINKSENSOR transmission line is correctly connected
to the AnyWireASLINK transmission line (DP, DN).
- Are the AnyWireASLINK master unit and slave unit powered by a power supply
with the appropriate capacity?
→
Confirm the power supply.
- Did you perform teaching?
→
Perform teaching settings with the work that is actually detected.
- Are you using within the rated detection range?
→
Use within the rated range.
- Is wiring correct?
→
Reconfirm the ASLINKSENSOR transmission line connection.
- Is power fed to the AnyWireASLINK system?
→
Confirm the power supply.
- Is the set parameter correct?
→
Check the parameter and set the correct parameter.
[Parameters and items]
Parameter
Default
variable
Variable
Details
[01.]
M12 : 18
M18 : 24
M30 : 26
M12 : 19
M18 : 25
M30 : 27
Set the threshold of the sensing level
to judge presence/absence of detection.
0 - 100%
Threshold
[02.]
5
Set change amount of sensing level
required to turn detection state ON to OFF.
0 - 100%
Hysteresis
[03.]
80
Set an upper limit for the alarm
judgment value.
0 - 100%
Alarm value Hi
[04.]
Set a lower limit for the alarm
judgment value.
0 - 100%
Alarm value Lo
[05.]
50
Set a monitor time for the alarm
judgment value. (1 = 100ms)
3-255
Alarm value
monitor time
[06.]
0
Normally open
Normally close
0
Normally open/
Normally close
[07.]
0
Simple mode
Normal mode
0
Operation
mode
[10.]
0
Delay timer disabled
ON delay timer
Delay timer
ON/OFF
[11.]
0 - 255
Set the delay time. (1 = 10ms)
0
Delay timer
value
1
1
0
1
OFF delay timer
ON/OFF delay timer
2
3