background image

-BSK4117M**1K  7/9-

LINK (Green)

IN (Orange)

ALM (Red)

LINK

(Green)

LINK

ALM

IN

(Orange)

Name

Indication status

ALM

(Red)

Details

Transmission signal is appropriately supplied

Sensing level drop*

Slave unit voltage drop

Transmission signal error

No transmission signal

Normal

When the master unit found that 

the ID (address) of this unit is duplicate 

or is not set.

ON

OFF

Flashing

On
Flashing

(On for 0.2 seconds, 

off for 1.0 second)

(0.1 seconds alternately)

Alternate flashing

On

Off

Off

On

Off

Teaching abnormality

Flashing

LINK
ALM

* Only when alarm diagnosis function is enabled

Setting for operation mode change

Setting for delay timer value

Setting for delay timer ON/OFF

If you set the delay timer in parameter 10, you can set the delay time.

Set if there is an alarm diagnosis function.

Variable

Details

0

Simple mode

Alarm diagnosis function disabled

Alarm diagnosis function enabled

1

Normal mode

- Address writer (ARW-04, ARW-03): Parameter 07

Default: 0

Variable

Details

0

No delay timer

Delay timer disabled

1
2
3

ON delay timer

ON/OFF delay timer

ON/OFF delay timer enabled

OFF delay timer

ON delay timer enabled

OFF delay timer enabled

- Address writer (ARW-04, ARW-03): Parameter 10

Default: 0

Set the ON delay timer/OFF delay timer.

0 - 255

Default: 0

- Address writer (ARW-04, ARW-03): Parameter 11

Normally open/Normally close setting

Variable

Details

0

Normally open

ON with work present

Set the normally open/normally close.

1

Normally close

ON with work absent

Alarm value Hi setting

Alarm value monitor time setting

Alarm value Lo setting

Set an upper limit for the alarm judgment value.

Set a lower limit for the alarm judgment value.

Set a monitor time for the alarm judgment value.

* Set the alarm values so that Hi is greater than Lo.

* Set the alarm values so that Hi is greater than Lo.

Default: 80

- Address writer (ARW-04, ARW-03): Parameter 03

Default: 50

- Address writer (ARW-04, ARW-03): Parameter 04

- Address writer (ARW-04, ARW-03): Parameter 05

- Address writer (ARW-04, ARW-03): Parameter 06

Variable

0 - 100

Unit

%

Variable

0 - 100

Unit

%

Variable

3 - 255

Unit

100ms

Default: 0

Variable

Unit

10ms

Default: BS-K4117-M12-1K : 19

BS-K4117-M18-1K : 25
BS-K4117-M30-1K : 27

CAUTION

Parameters [08, 09, 12 to 19] are items related to 
internal settings. Do not perform settings.

[Monitor display]

Displays the operation status of this product using the LEDs.

Normal state: LINK flashing, ALM off, IN ON on/OFF off

Содержание ASLINKSENSOR BS-K4117-M 1K Series

Страница 1: ...circuit or similar problem in the hybrid unit including the output unit and the output circuit may result in smoke generation or fire An external safety device such as a fuse must be installed System power supply Use a stabilized 24V DC power supply Use of a non stabilized power supply may cause problems with the system Separately route high voltage and power cables Although the AnyWireASLINK has ...

Страница 2: ...for the AnyWireASLINK according to the load current This Products Guide describes a two wire non isolated terminal If the load current is small using a two wire non isolated terminal allows for achieving simplified wiring without a local power supply If you are prioritizing the sites of concentrated loads or the number of units connected hybridization with a four wire isolated terminal which suppo...

Страница 3: ... EAC 06 472 MAX 6A 24V DC Model Type Allowable power current Filter allowable power current Insert the ASLINK filter Type ANF 01 regardless of installation method and distance when complying with CE Standard General purpose power supply filter Use if necessary General purpose power supply filter Use if necessary POWER IN SLAVE The figure is an explanatory schematic Adjust the actual terminal layou...

Страница 4: ...re terminal Four wire terminal DP DN 24V 0V Four wire terminal Four wire terminal DP DN 24V 0V Four wire terminal DP DN 24V 0V Four wire terminal 24V 0V 24V 0V PE AnyWireASLINK master 24V 0V L N FG 24V DC stabilized power supply 24V 0V 24V 0V PE DP DN 24V 0V Four wire terminal DP DN 24V 0V Four wire terminal A B General purpose power supply filter Use if necessary General purpose power supply filt...

Страница 5: ...and then hitch the hook C to fix the cover Insert the body clamp into the hole of the cover and crimp them with a dedicated tool For the LP4 WW 10P perform crimping with pin 1 for DN pin 2 for DP and pins 3 and 4 empty After crimping check that the hooks to are securely engaged With cover mounted Check that the hooks and are engaged Installation Location Precautions for Use If you expect you will ...

Страница 6: ...etting is changed in the WRITE mode the setting is reflected after the system is re started up When setting is changed in the DIRECT WRITE mode the setting is reflected at the time when the writing is completed If this unit is included in a parallel arrangement use the remote head ARW RH together and ensure that writing is not performed to terminals not intended Make sure to use a 24V DC stabilize...

Страница 7: ...timer ON delay timer enabled OFF delay timer enabled Address writer ARW 04 ARW 03 Parameter 10 Default 0 Set the ON delay timer OFF delay timer 0 255 Default 0 Address writer ARW 04 ARW 03 Parameter 11 Normally open Normally close setting Variable Details 0 Normally open ON with work present Set the normally open normally close 1 Normally close ON with work absent Alarm value Hi setting Alarm valu...

Страница 8: ...as shown below ASLINKSENSOR is not connected to an AnyWireASLINK system Power supply for the AnyWireASLINK system itself is not turned on Directly connected to 24 0V power supply The ASLINKSENSOR maintains the address number 255 default setting The ASLINKSENSOR has an address redundant with another unit Transmission signal level reduction has been detected The sensing level has been reduced Confir...

Страница 9: ...2017 UMA 16717A EN Outside Dimensions Unit mm BS K4117 M18 1K BS K4117 M12 1K BS K4117 M30 1K Transmission cable Oil resistant flex resistant type φ29 24 1000 15 5 35 4 10 17 M18X1 Red DP Black DN Transmission cable Oil resistant flex resistant type Red DP Black DN φ21 17 35 5 3 10 15 4 1000 11 M12X1 10 5 Red DP Black DN M30X1 5 43 36 φ42 17 6 1000 Transmission cable Oil resistant flex resistant t...