27 (70)
8.3
Diagnostic Object (02h)
Category
Basic
Object Description
This object provides a standardized way of handling host application events & diagnostics, and is thoroughly
described in the general
Anybus CompactCom 40 Software Design Guide
.
See also ...
•
Supported Commands
Object:
Get_Attribute
Create
Delete
Instance:
Get_Attribute
Object Attributes (Instance #0)
#
Name
Access
Data Type
Value
1... 4
-
-
-
Consult the general Anybus CompactCom 40 Software Design
Guide for further information.
11
Max no. of instances
Get
UINT16
5+1 (Of the maximum number of instances there should always
be one instance reserved for an event of severity level ‘Major,
unrecoverable’, to force the module into the ‘EXCEPTION’-
state.)
12
Supported
functionality
Get
BITS32
Bit 0: “0” (Latching events are not supported)
Bit 1 - 31: reserved (shall be “0” )
Instance Attributes (Instance #1)
Extended
#
Name
Access
Data Type
Value
1
Severity
Get
UINT8
Consult the general Anybus CompactCom 40 Software Design
Guide for further information.
2
Event Code
Get
UINT8
3
-
-
-
Not implemented in product
4
Slot
Get
UINT16
Consult the general Anybus CompactCom 40 Software Design
Guide for further information.
5
ADI
Get
UINT16
6
Element
Get
UINT8
7
Bit
Get
UINT8
Anybus
®
CompactCom
™
40 Modbus-TCP
®
Transparent Ethernet Network Guide
SCM-1202-022 1.1