Antti-Teollisuus Oy
15
408102 02-2020
Vacboost WM09
Dryer Heater
Installing the temperature measuring facility
Pull the PTC sensor (1) with its conductors (4)
through the nylon pipe (2) so that the metal
part of the sensor sticks out about 20 mm
from the nylon pipe.
Drill a hole of 10.5 mm in the air pipe, and
install the lead-through gasket (3) in it.
Push the nylon pipe with the sensor through
the lead-through gasket into the air pipe;
about 20 mm of the nylon pipe shall be
sticking out.
Connect the sensor to the system in accor-
dance
with the wiring diagram. Carry out the
connection in a separate connecting box (not
included in the delivery).
The type of temperature measuring facility depends on the configuration of the machinery. The measuring of the
temperature can be realised, either by means of a PTC-sensor or a temperature transmitter.
Install the temperature transmitter (4) in the air pipe using the
installation flange (3). Drill an 8 mm hole (1) in the inlet air
pipe. Fix the installation flange at the hole in the pipe, using
self-tapping screws (2). Insert the sensor of the temperature
transmitter into the pipe through the installation flange, and
tighten it in place with the lock screw (5)
HOLE