18IP22B
12
2.4 Water heater protection
Configuration level
Parameter
Display
Factory setting
Analog input 1, 2 and 3; setpoint changeover / shift
C111
9930
Limit comparator; controller type; setpoint 1; locking
C112
5010
Unit address; decimal place / unit signal for out-of-range
C113
0
Measurement range start analog input 1
SCL
0
1
Measurement range analog input 1
SCH
100
1
Measurement range analog input 2
SCL2
0
1
Measurement range analog input 2
SCH2
100
1
Lower setpoint limit
SPL
30
1
Upper setpoint limit
SPH
95
1
Actual value correction, analog input 1
OFF1
0
1
Actual value correction, analog input 2
OFF2
0
1
Actual value correction, analog input 3
OFF3
0
1
Filter time constant for digital filter, analog input 1
dF1
1
These parameters are affected by the setting for the decimal place.
1
The R18 is protected by the following systems:
minimum water flow switch
The water flow switch is installed in the flow manifold and
continuously monitors the minimum water flow. If the water flow
falls below a preset level, the burner is shut down and will go to
lock-out. The water flow switch is factory set and should not be
adjusted.
high limit thermostat (E.C.O.)
In the event of failure of the control thermostat, a preset high
limit thermostat will shut down the burner and go to lockout.
pressure relief valve
The maximum operating pressure of the R18 water heater is 10
bar. The standard safety valve supplied is
set to 5 bar
. If a
different pressure setting is required this should be specified
and will be set at the factory.
gas burner control
The burner control unit provide control and supervision of the
atmospheric burner. The sequence controller is coupled to the
spindle of the control circuit and to the flame supervision unit
displaying the status, the symbol appearing above the reading
mark indicates the firing sequence or lock-out condition. The
pilot flame is supervised by ionisation current detection.
Содержание R18 Series
Страница 5: ...18IP22B V Fig 2 Dimensions 500 litre tank R18 SUPA FLO PLUS with BT 500 litre tank...
Страница 6: ...18IP22B VI...
Страница 68: ...18IP22B 60...
Страница 69: ...18IP22B 61...
Страница 70: ...18IP22B 62...
Страница 71: ...18IP22B 63...