18IP22B
III
R18 WATER HEATER TECHNICAL DATA
Type
132
154
180
210
244
280
Nominal heat output
kW
481
558
649
756
875
1002
Nominal heat input (nett. CV)
kW
538
625
727
846
980
1122
Gas consumption
natural gas H (
10,9 kWh/m
)
m /h
49,3
57,9
67,4
78,4
90,8
104,0
3
propane
m /h
19,0
22,1
25,7
29,9
34,7
39,7
3
3
Gas inlet pressure
(min.)
mbar
17
17
17
17
17
17
(max.)
mbar
25
25
25
25
25
25
propane (max.)
mbar
50
50
50
50
50
50
Water volume
dm
22,0
23,2
24,6
26,3
28,1
30,1
Max. working pressure
bar
11
11
11
11
11
11
3
Flue connection
D
mm
450
500
550
600
650
700
Gas connection
G
2"
2"
2"
2"
DN65 PN16 DN65 PN16
Water connections
cold water feed + hot water flow W
DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
recirculation
DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
Pressure relief valve
connection
1¼”
1¼”
1¼”
1½”
1½”
1½”
relief connection
1½”
1½”
1½”
2"
2"
2"
standard setting
bar
5
5
5
5
5
5
Electrical supply
water heater 1N~
V
230
230
230
230
230
230
pump 3N~
V
400
400
400
400
400
400
Frequency
Hz
50
50
50
50
50
50
Fuse
A
6
6
6
6
6
6
Max. electrical consumption
water heater
kW
0,04
0,04
0,04
0,04
0,04
0,04
pump
kW
0,75
0,75
0,75
0,75
0,75
0,75
Dimensions
B
mm
1430
1430
1430
1430
1400
1400
H
mm
1795
1795
1795
1795
1895
1895
L
mm
1461
1636
1842
2080
2350
2636
Weight, empty, ± 5 %
kg
620
660
705
760
820
885
Table 1 Technical Data
- Heat output measured with :
60 - 80 °C
- Gas consumption at
:
1013 mbar, 15 °C, dry
- Gas
specification
:
II
2H3P
- Appliance category
:
B11
- Protection
degree
:
IP30
Changes in specifications and dimensions
The manufacturer reserves the right to change the above mentioned dimensions without prior
notice.
Because of manufacturing tolerances, the above mentioned dimensions can vary slightly.
Содержание R18 Series
Страница 5: ...18IP22B V Fig 2 Dimensions 500 litre tank R18 SUPA FLO PLUS with BT 500 litre tank...
Страница 6: ...18IP22B VI...
Страница 68: ...18IP22B 60...
Страница 69: ...18IP22B 61...
Страница 70: ...18IP22B 62...
Страница 71: ...18IP22B 63...