18IP22B
46
Fault
Possible cause
Solution
Air modulating damper
HT lead disconnected or
Correct
cycles, no ignition spark
faulty
and water heater then
goes to lockout, indicator
Ignition electrode incor-
Check setting or replace
(2) alights
rectly set or faulty
Faulty ignition generator
Change
Faulty control box
Change box
Ignition sparks, pilot
Gas supply turned off
Turn on
burner does not light and
water heater then goes
Pilot manual cock turned
Turn on
to lock-out indicator (2)
off
alights
Air in gas line
Purge air
Faulty pilot safety shut
Rectify
off valve or Connections
Pilot injector blocked
Clean
Pilot governor set too low
Adjust
Pilot burner ignites but
Check flame probe
If damaged, replace
water heater then goes
to lock-out, indicator (2)
Flame probe lead(s) not
Rectify
alights. Main burners do
connected or faulty
not light
Faulty connections to
Rectify
main safety shut off val-
ve(s)
Faulty main safety shut
Change valves
off valves
Faulty control box
Replace
Check ionisation current,
as per instructions
Water heater operates
Fault in water system
Rectify
but then goes to over-
heat indicator (4) alights
Main burner pressure set
Reset
too high
Pump overrun inopera-
Rectify
tive
Water heater does not
Min. fire is set below
shut down
minimum setting, reset
servomotor.