18IP22B
38
Adjusting the burner pressure
The burner pressure must be adjusted when the water heater
has been running for 20 minutes at high load (state of equilib-
rium).
Natural gas H (G20)
Gas service pressure 20 mbar
Nozzle diameter 1,85 mm
minimum load (20 %)
Type
Burner
Pilot
Air damper
pressure
pressure
opening
(mbar)
(mbar)
(mm)
closed
132
0,8
3,5
8
154
0,8
3,5
8
180
0,8
3,5
8
210
0,8
3,5
8
244
0,8
3,5
8
280
0,8
3,5
8
full load (100 %)
Type
Burner
Pilot
Air damper
pressure
pressure
opening
(mbar)
(mbar)
(mm)
maximum
open
132
10,5
3,5
125
154
10,4
3,5
125
180
10,2
3,5
125
210
10,0
3,5
125
244
9,9
3,5
125
280
9,8
3,5
125
Table 15a
Burner pressure Natural gas
Содержание R18 Series
Страница 5: ...18IP22B V Fig 2 Dimensions 500 litre tank R18 SUPA FLO PLUS with BT 500 litre tank...
Страница 6: ...18IP22B VI...
Страница 68: ...18IP22B 60...
Страница 69: ...18IP22B 61...
Страница 70: ...18IP22B 62...
Страница 71: ...18IP22B 63...