NEO
fl
o
Water
Heater
16
September
2015
Th
e
fl
ue discharge position for any
fl
ue type must conform to the following requirements
Minimum
Distance
mm
A Directly below an opening, air brick, opening window etc.
300
B Above an opening, air brick, opening window etc.
300
C Horizontally to an opening, air brick, opening window etc.
300
D Below a gutter or sanitary pipework
75
E Below the eaves
200
F Below a balcony or carport roof
200
G From vertical drain/soil pipework
150
H From an internal or external corner
300
I Above ground, roof or balcony level
300
J From a surface facing terminal
600
K From a terminal facing the terminal
1200
L From a opening in a carport (e.g. door, windows) into the building
1200
M Vertically from a terminal on the same wall
1500
N Horizontally from a terminal on the same wall
300
FLUE TERMINAL POSITIONS
Fig 6.6