NEO
fl
o
Water
Heater
12
September
2015
FLUE SYSTEMS
Th
e appliance can be installed using a number of alterna-
tive arrangements depending upon the installation re-
quirements It is delivered with its two 80 mm connection
points combined into a 80/125 concentric outlet on the
left. Flue components are ordered separately as required.
Available Flue Types
Open Flue (Type B
23
)
Th
is is an open
fl
ued arrangement where the air for com-
bustion is drawn from the Water Heater room and because
of this the room must be ventilated. If the Heater is
installed in a compartment then it will require both a high
level and a low level vent. See Page 17.
Th
e
fl
ue products are discharged either horizontally or
vertically using any of the supplied separate duct compo-
nents.
Room Sealed (Type C
xy
)
Th
ere are a two approved room sealed arrangements
where both the air inlet and
fl
ue discharge terminate
outside the building.
Type C
13
Flue and air ducts terminate horizontally in the
same position
Type C
33
Flue and air ducts terminate vertically in the
same position
Flue and air ducts are supplied to a concentric design
(80/125). See Fig. 6.1 for component choices.
Flues should slope back to the Heater by 3 degrees.
Terminal positions must comply with the requirements
detailed in Fig. 6.6.
FLUE EQUIVALENT LENGTH CALCULATION
Th
e combustion fan
fi
tted to the appliance moves the air
and
fl
ue products through the system and can provide
suf
fi
cient capacity for a
Flue
Equivalent Length
(
FEL
) of
20 metres for type
C
13
and
C
33
systems and 40 metres for
type
B
23
system.
Each
fl
ue accessory such as bends and straight lengths
restrict the
fl
ue system and have a
FEL
which must be
added together to determine the total.
NB:
For
C
13
and
C
33
systems the Terminal and the Twin
Flue to Concentric Adapter do not have to be included,
they have already been taken into account.
Referring to the diagrams Fig. 6.2, 6.3, 6.4, 6.5 select a
suitable
fl
ue system for the particular installation require-
ment and then calculate the
FEL
of the system, this must
not be greater than that stated above.
Examples:
A
C
33
Concentric
fl
ue system that uses one straight length
and one 90° bend.
1 x 1m straight length
1.0
1 x 90° bend
1.5
Total
(within 20m limit)
2.5
A
C
13
or
C
33
Concentric system that rises from the Heater and
uses eight straight lengths and seven 90° bends.
8 x 1m straight lengths
8.0
7 x 90° bends
10.5
Concentric Adapter
0.0
Terminal
0.0
Total
(within 20m limit)
18.5
Open Flue Type B
23
Th
e maximum
FEL
of
fl
ue in this con
fi
guration is 40 metres.
Th
e air inlet connection to the appliance must be
fi
tted with
a Debris Guard. Air is drawn from the room or compartment
in which the heater is installed and therefore the room or
compartment
must be ventilated.
See Page 17.
Th
e
fl
ue duct can discharge either vertically or horizontally
by selection of the correct
fl
ue terminal.
Th
e
fl
ue pipe can
be
fi
tted with 90 and 45 degree bends as well as exten-
sions.
Example:
A
B
23
system with air collected from the plant room and the
fl
ue exiting via four straight length and four 90° bends to a
roof terminal.
4 x 1 m straight lengths of FLUE.
4.0
4 x 90° bends of FLUE
14.0
1 x Roof Terminal
6.6
Total
(within 40m limit)
24.6
Flue support
All installed
fl
ues, vertical or horizontal, should be sup-
ported every 1m using the appropriate brackets.
Fixing the Wall Terminal
A hole size of 175mm is recommended.
Th
e terminal should
be installed with a three degree slope back to the Heater
and the gap around it
fi
lled with mortar, both on the inside
and outside. (See Fig 6.5). Wall plates can then
fi
xed inside
and out to present a clean
fi
nish.
Fixing a Vertical Terminal
A suitable
fl
ashing for the roof angle should be selected and
fi
tted to the vertical terminal.
Th
e Terminal should then be
fi
tted to the roof, securing it from below with the appropri-
ate bracket. (See Fig 6.5)
Содержание NEOflo SC25/200
Страница 32: ...Published date November 2015...