UG-076
Evaluation Board User Guide
Rev. A | Page 10 of 16
FEEDBACK (N) DIVIDER WINDOW
The
N Divider
window shown in Figure 14 is accessed by
clicking the
N DIVIDER
box. It allows the user to set the
feedback divider. If this box is colored gray, the PLL is off. To
turn the PLL on, click the
PLL MODE
box at the top of the
main window and select
Norm Op
.
087
46-
01
0
Figure 14.
N Divider
Window
The various modes of the N divider are described in detail in
the
data sheet. For most applications, the 8/9 or 16/17
dual modulus modes are used. For applications requiring a
divider value larger than 131119, the 32/33 mode is provided.
Different applications require different settings, and the user
can experiment with the different settings.
The evaluation software has internal checking to ensure that
invalid settings are not programmed. For example, the B
counter must always be larger than the A counter. Another
restriction is that 8/9 dual modulus mode cannot be used for
VCO frequencies greater than 2400 MHz. In cases where a
feedback divider restriction cannot be resolved, the user may
need to adjust the R (reference) divider to allow a different
feedback divider value. For example, it is not possible to use the
internal VCO and a feedback divider of 30. However, the R
divider can be doubled, which allows a feedback divider of 60.
The feedback divider window has a check box for holding the N
divider in reset. When the N divider is held in reset, the PLL is
open. Therefore, this feature is seldom used.
R AND N DELAY WINDOW
The N delay window shown in Figure 15 is accessed by clicking
the
N DELAY
box on the main window. The
R DELAY
box is
identical to the
N DELAY
box. These delay settings, which are
most often used in zero delay mode, allow the user to vary the
static phase offset of the PLL.
087
46
-0
11
Figure 15. N Delay Window
PHASE FREQUENCY DETECTOR (PFD) WINDOW
The
Phase Frequency Detector (PFD)
window shown in
Figure 16 is accessed by clicking the
PFD
box in the main window.
08
74
6-
01
2
Figure 16.
Phase Frequency Detector
Window
The features accessible in this window are described in detail in
the
data sheet. The most commonly used settings are
Anti-Backlash Pulse Width
and
Lock Detect Counter
.
For phase detector frequencies greater than 50 MHz, the PLL
may work better with the 1.3 ns antibacklash pulse width
setting.
Setting the
Lock Detect Counter
to values greater than 5 PFD
cycles can be useful in applications where the loop bandwidth is
low and the lock detect counter chatters during acquisition.