Page 54
EWCIE Technical Manual
The following shows the outputs
There are 8 outputs, one per amplifier.
The amplifier can be programmed for zone and global action.
For zone action, the fire zone that will activate the amplifier is shown in the bottom right hand corner of
the dialogue box. This field is editable. The action type can be set by the tick boxes. Normally the EWCIE
will be activated by a Fire action type.
The global action, only an action type is specified. Most EWCIE will be assigned global Fire.
All other fields on the dialogue box have no impact.
Each amplifier is activated according to the DIP switch setting in section 5.6 – except setting 7 (111) is
NOT
supported.
For more specialised programming, the amplifiers can be programmed via cause and effect.