Page 36
EWCIE Technical Manual
10.7.4 Fault Diagnostic table – Internal - Engineer
Orange LED
Diagnostic
Green LED
Mains
Condition
Possible Cause
Action
Off
On
Normal
operation
Mains present
Battery fully charged
None
Off
Standby
Operation
Mains Lost. No faults
present
Battery driving load
Investigate loss of mains
Flash Continuous
On or Off
No output
Output fuse blown
Output overload
Output short circuit
Check and replace output fuse
Disconnect output load and
test load
1 Pulse
On
Battery
Charging
No faults active
Battery charging
normally but < 90% of
full charge
None
2 Pulses
On
No Battery
Battery disconnected
Battery fuse blown
Battery heavily
discharged
Check battery connections
Check battery fuse
Check battery condition
Replace battery if aged
Off
Low Battery
Volts
Standby Mode
Battery almost
discharged
Restore mains
3 Pulses
On or Off
Battery Fault
High impedance in
battery connection
Battery internal fault
Check battery connections for
corrosion. Replace battery if
aged
4 Pulses
On or Off
Charger
Fault
Internal failure of
battery charger
Return to manufacturer
5 Pulses
On or Off
Battery
Temperature
Probe Fault
Battery temperature
monitor disconnected
or damaged
PSU running in Safe
Mode
Check temperature sensor
connections and condition of
sensor.
Replace if suspect
10.8 6050-0008 EvacU Standalone Isolation 50W Amplifier
(NOTE: ONLY FOR USE ON EV3000 AND EV100 AMPLIFIERS)
Where there is a requirement that an isolated amplifier is required the Standalone Isolation amplifier can
accommodate most instances. This unit connects to an EV3000 100V amplifier line circuit and
reproduces the signal produced using a battery backed 50w amplifier mounted inside the remote
cabinet.
It can be used for secure line applications or to add additional capacity to an already loaded circuit.
The internal 100V output line is monitored for shorts and interruptions. Any fault present within the
standalone system will be transferred to the 100V source input line via a switching resistor.
A local background music input is provided on the isolation amplifier for individual tenancy applications.
This allows the installer to have background music playing on the remote isolation amplifier zone. In the
event of the source 100V line being triggered the background music will be switched out for the priority
of the source 100V line.
(NOTE: Line monitoring for 120W amplifiers is only compatible with
amplifiers manufactured post 2016)
Output volume and VOX Input sensitivity can be adjusted via the pots on the 100V to line level convertor.
Output Volume
Input VOX Sensitivity
For instructions on mains connection and power up please follow
Section 10.4.2 - 5 AMP PSU
For field connections see below drawing.
Содержание EvacU
Страница 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Страница 30: ...Page 29 EWCIE Technical Manual 10 3 Panel General Layouts Figure 11 Standalone 25W with 3Amp PSU shown ...
Страница 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Страница 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Страница 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Страница 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Страница 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Страница 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Страница 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...
Страница 60: ...Page 59 EWCIE Technical Manual ...