Page 33
EWCIE Technical Manual
10.4.3 10 Amp PSU
Figure 16: 10 Amp PSU shown
Figure 17: 10 Amp PSU Battery Selection Links
Select the Battery type by placing the link (above the Battery fuse) in the appropriate location
to select (17/18 Ah, 38/40 Ah or 65 Ah) batteries. This changes the maximum bulk charge
current, and therefore enables higher load current to be used when smaller batteries are
required. Put the link on the left hand two pins for 17/18 Ah, the middle pins for 38/40 Ah and
the right hand two pins for 65 Ah batteries
With mains
disconnected,
connect the two 12 V standby batteries in series using the single
cable provided. Connect the
negative
of one battery to the
positive
of the other.
DO NOT
CONNECT
the other two battery terminals to each other.
Connect the free Positive and Negative terminals of the batteries to the PCB terminals Batt+
and Batt - using the cables provided.
Apply mains and, after the LED indicators initial start-up flash, verify that the yellow Fault LED
does not flash (battery connection detected).
Disconnect the mains power. Verify that the green Mains LED extinguishes and the yellows
Fault LED starts to pulse (indicating that the PSU is running from its standby batteries).
Verify that the EWCIE Front Control indicates a fault.
Reconnect the mains. Verify that the green Mains LED illuminates and the yellow Fault LED
extinguishes
Figure 18: 10 Amp PSU Terminals shown
Note
:
For further 10A PSU specifications refer to MAN3087
Содержание EvacU
Страница 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Страница 30: ...Page 29 EWCIE Technical Manual 10 3 Panel General Layouts Figure 11 Standalone 25W with 3Amp PSU shown ...
Страница 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Страница 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Страница 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Страница 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Страница 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Страница 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Страница 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...
Страница 60: ...Page 59 EWCIE Technical Manual ...