4.5.3 Test
Activating the TEST control places the EWCIE into the TEST condition.
There are three different Test Modes.
Test Mode 1
:
Momentarily pressing the Test button places the EWCIE into Test Mode 1.
This test mode allows for testing the processing and indication of alarm input signals and manual
controls for ALL Emergency Zones.
All audio (Alert, Evac, live speech and recorded messages) will NOT be broadcast to any Emergency
Zones.
Test Mode 2
:
Press and hold the Test button until the buzzer sounds twice and the Test indicator flashes twice
(approx. 6 seconds) will place the EWCIE into Test Mode 2.
This test mode provides an Audible Test Tone that is broadcast to ALL Emergency Zones.
However, if a Zone Module is used, pre-selecting certain Zones by pressing the zones associated
“Speech” button allows the Audible Test tone to be sent to the selected zones only instead of All zones.
Test Mode 3
:
Press and hold the Test button until the buzzer sounds three times and the Test indicator flashes three
times (approx. 12 seconds) will place the EWCIE into Test Mode 3.
This test mode when a Zone indicator module is used, provides the ability to place certain zones into a
test state that allows the broadcasting of Alert, Evac, speech and recorded messages to the selected
zones.
To remove the EWCIE from the TEST condition, activate the TEST control (toggle function) or activate
the RESET control.
The EWCIE will only recognise the TEST control when it is NOT broadcasting any audio – including pre-
recorded messages and live speech.
The Test control is operational at access level 2.
Содержание EvacU
Страница 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Страница 30: ...Page 29 EWCIE Technical Manual 10 3 Panel General Layouts Figure 11 Standalone 25W with 3Amp PSU shown ...
Страница 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Страница 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Страница 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Страница 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Страница 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Страница 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Страница 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...
Страница 60: ...Page 59 EWCIE Technical Manual ...