Page 18
EWCIE Technical Manual
5.9 System Messages
The EWCIE amplifier/tone-generator shall have standard system messages programmed by default.
They cannot be overwritten. These messages are shown in the table below.
Message
Length
Description
Evacuation
“Emergency – Evacuate Now” (for AS1670.1 and NZS4512)
Alert
6s
“An incident has been detected in the building – please prepare to evacuate
and wait further instructions” (for AS1670.1 and NZS4512)
False Alarm
8s
“May I have your attention please – A false alarm has been detected. The
all clear is now given. Thank you for your patience and understand”
System Test
4s
“This is a fire alarm test”
Lockdown
3s
No Message (tone only)
5.10 Custom Messages
The EWCIE can have custom messages programmed. For details on how to program and use custom
messages refer to section 9 and 10 of the OWS Programming Manual MAN3084.
Содержание EvacU
Страница 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Страница 30: ...Page 29 EWCIE Technical Manual 10 3 Panel General Layouts Figure 11 Standalone 25W with 3Amp PSU shown ...
Страница 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Страница 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Страница 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Страница 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Страница 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Страница 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Страница 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...
Страница 60: ...Page 59 EWCIE Technical Manual ...