Page 16
EWCIE Technical Manual
5.6 DIP switch settings
The Amplifier has two DIP switches Configuration switches (SW3) and Address Switches (SW4)
The Configuration DIP switch (SW3) is 8-way and has the following options:
Switch 1
Commissioning Mode
*(Dynamic)
Set to On (1) for Commissioning Mode
Off (0) for Operation Mode
Default is On (1)
Refer to 5.8 volume controls for detail on commissioning mode
Switch 2 & 3
Country Standard
*(Start Up)
2 Off (0) & 3 Off (0) – AS1670.1:2015
2 Off (0) & 3 On (1) – NZS4512:2010
2 On (1) & 3 Off (0) – N/A
2 On (1) & 3 On (1) – Custom Configuration
Default is switch 2 and 3 Off
Switch 4
Background Music Mode
*(Dynamic)
Set to On (1) to enable the RPC (+ and -) audio inputs to be
used for background music.
Switch 5, 6 & 7
Alert/Evac Timeout &
Custom Input settings
*(Start Up)
Configures how the EWCIE responds to the alarm signal
Option 5,6,7
0.
(000) 0s timeout – Evac signal only
1.
(001) 60s Alert signal, then Evac signal
2.
(010) 90s Alert signal, then Evac signal
3.
(011) 120s Alert signal, then Evac signal
4.
(100) 180s Alert signal, then Evac signal
5.
(101) 300s Alert signal, then Evac signal
6.
(110) no timeout – Alert signal only
7.
(111) Set for Custom Input Configuration - refer to
EvacUwiz Programming Manual MAN3084.
Switch 8
Earth Fault detection.
Stand Alone Panel Only
*(Dynamic)
Set to On (1) for Detect Earth Fault; Off (0) to Disable. Default
is Off (0).
The Address DIP switch (SW4) is 4-way and has the following options:
Switch 1,2 & 3
Communication Address
*(Start Up)
Local Amplifier Address (valid range is 0 to 7);
Set to a unique valid address for each EWCIE
connected to the Local Bus (CAN).
Option 1,2,3
0.
(0 0 0) Emergency Zone 1
1.
(0 0 1) Emergency Zone 2
2.
(0 1 0) Emergency Zone 3
3.
(0 1 1) Emergency Zone 4
4.
(1 0 0) Emergency Zone 5
5.
(1 0 1) Emergency Zone 6
6.
(1 1 0) Emergency Zone 7
7.
(1 1 1) Emergency Zone 8
Default is 0; First amplifier must be 0.
Switch 4
Communication Monitoring
*(Dynamic)
Set to On (1) to enable monitoring of the
communications path between the amplifier and an
associated front panel.
Set to On (1) if a front panel switch and indicator card
is fitted. A general fault (indicator and relay) will be
activated if communications is lost with the front
panel.
Should be set to Off (0) is no front panel is fitted.
Содержание EvacU
Страница 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Страница 30: ...Page 29 EWCIE Technical Manual 10 3 Panel General Layouts Figure 11 Standalone 25W with 3Amp PSU shown ...
Страница 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Страница 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Страница 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Страница 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Страница 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Страница 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Страница 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...
Страница 60: ...Page 59 EWCIE Technical Manual ...