11.6 Heat Insulation 

1.  Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. 

Please wrap the insulated piping end to prevent water from going inside the piping. 

2.  If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using 

POLY-E FOAM with thickness 6 mm or above. 
 

 

Refrigerant tubing shall be protected against mechanical damage. 

 

Liquid-side pipes 

 

CAUTION

 

Use a material with good heat-resistant properties as the heat insulation for the 
pipes. Be sure to insulate both the gas-side and liquid-side pipes. If the pipes are 
not adequately insulated, condensation or water leakages may occur. 

 

Gas-side pipes 

Material shall 
withstand 
120°C or higher 

 
CUTTING AND FLARING THE PIPING 

1.  Please cut using pipe cutter and then remove the burrs. 
2.  Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. 

Turn the piping end down to avoid the metal powder entering the pipe. 

3.  Please make flare after inserting the flare nut onto the copper pipes. 

 

1. To cut

■ Improper flaring ■

Inclined Surface

damaged

Cracked Uneven

thickness

Bar

Red arrow mark

Handle

Core

Yoke

Clamp
handle

Bar

0 – 0.5 mm

Copper pipe

When properly flared, the internal surface
of the flare will evenly shine and be of
even thickness. Since the flare part comes
into contact with the connections, carefully
check the flare finish.

Reamer

2. To remove burrs

3. To flare

Point down

Pipe

 

11.6.1 

Disposal Of Outdoor Unit Drain Water 

  If a drain elbow is used, the unit should be placed on a stand which is taller than 5 cm. 

  If the unit is used in an area where temperature falls below 0°C for 2 or 3 days in succession, it is recommended 

not to use a drain elbow, for the drain water freezes and the fan will not rotate. 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание CU-4Z80 Series

Страница 1: ...iping Amin M 2 5 LFL 5 4 h0 2 Amin Required minimum room area in m2 M Required charge amount in appliance in kg LFL Lower flammable limit 0 306 kg m3 h0 Installation height of the appliance 1 8 m for...

Страница 2: ...Unit Installation Diagram 1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut 10 mm 2 When installing at roof please consider strong wind and earthquake Please fasten the ins...

Страница 3: ...side of CS MZ16 CS TZ25 CS MTZ16 CS TZ35 CS Z20 CS TZ42 CS Z25 CS TZ50 CS Z35 CS TE20 CS Z42 CS TE25 CS Z50 CS TE35 CS XZ20 CS TE42 CS XZ25 CS TE50 CS XZ35 CS E9 CS XZ50 CS E12 CS TZ20 CS E18 Liquid s...

Страница 4: ...if there is a constant pressure drop Move to next step Step 2 Refrigerant leak detection if there is any pressure drop Otherwise release the Nitrogen gas and move to Step 3 Evacuation of the equipmen...

Страница 5: ...ptor Outdoor unit Liquid side Gas side OPEN Vacuum pump Liquid side 3 way valve Gas side 3 way valve Liquid side Gas side Tube connector Tube connector Tube connector Tube connector Close Close Indoor...

Страница 6: ...s at the interface point are sufficient for the installation of the equipment CU 4Z80 Unit D Unit C Unit A Unit B Indoor Outdoor connection cable Power Supply Cord Isolating Devices Indoor Unit A Indo...

Страница 7: ...remove the burrs 2 Remove the burrs by using reamer If burrs is not removed gas leakage may be caused Turn the piping end down to avoid the metal powder entering the pipe 3 Please make flare after in...

Отзывы: