System Overview
|
1-11
Electronics
• Connections to the analyzer are made through the wiring card. The
wiring card is located on the right side in a separate section of the
analyzer.
• Analyzer wiring and customer wiring (power, I/O) are directly con-
nected to the main electronics.
• All connections are pluggable and headers are laser-printed for easy
matching.
•
The configuration monitoring interface is RS-485 MODBUS RTU.
I/O
The WDG-V UOP has the following I/O:
•
Three (3) configurable 4-20 mA outputs
• Two (2) system alarm relays (Service and Data Valid)
•
Three (3) configurable process alarm relays
• One (1) RS-485, 2 wire, MODBUS RTU interface (57.6K baud)
Current Output Connections
Standard Current Outputs
There are three current outputs on the WDG-V UOP analyzer. The cur-
rent output connections are labeled as follows on the analyzer board
terminals:
Analog Output #1 => +I1-
Analog Output #2 => +I2-
Analog Output #3 => +I3-
The current outputs are referenced as Analog Outputs 1, 2 and 3 in the
standard PC software and AMEVision Display User Interface. Each of the
current outputs is capable of driving up to 1000-Ohm loads.
Observe the polarity when connecting current output devices to
these terminals.
The current outputs can be selected for the following ranges:
0-20mA
4-20mA
NAMUR
!
CAUTION
Содержание Thermox WDG-V UOP
Страница 34: ...2 6 Thermox WDG V UOP IECEx ATEX This page intentionally left blank...
Страница 65: ...AMEVision Display Installation Guide 4 5 Customer I O Connections...
Страница 68: ...4 8 Thermox WDG V UOP IECEx ATEX This page intentionally left blank...
Страница 80: ...5 12 Thermox WDG V UOP IECEx ATEX This page intentionally left blank...
Страница 85: ...Service and Parts 6 5 Cell Clips Cell Housing Washer Cell O Ring Hex Nut Figure 6 2 Cell replacement...
Страница 87: ...Service and Parts 6 7 Speed Clips Thermocouple Thermocoouple Figure 6 3 Thermocouple replacement...
Страница 91: ...Service and Parts 6 11 Box Heater Block Furnace Wires Heater Figure 6 6b Box Heater Replacement...
Страница 96: ...6 16 Thermox WDG V UOP IECEx ATEX This page intentionally left blank...